CHANGE STATUS TO (COL) | | | 1/18/2008 | | DONE |
|
|
|
|
(F) Reprint permit | | | 11/15/2007 | | DONE |
|
|
|
|
INSP-Final Inspection | 4/30/2007 | 4/30/2007 | 4/30/2007 | P | PASS |
Troy Cobbley
|
|
|
permit finaled per Brian
|
INSP-Final Inspection | 4/27/2007 | 4/30/2007 | 4/30/2007 | A | PASS |
Troy Cobbley
|
|
|
permit finaled per Brian
|
INSP-Final Inspection | 4/27/2007 | 4/27/2007 | 4/27/2007 | P | FAIL |
Troy Cobbley
|
|
|
Per Brian the fire alarm system strobes do not sync and the remote indicators for the duct smoke detectors are wrong
|
INSP-Final Inspection | 4/25/2007 | 4/26/2007 | 4/27/2007 | A | FAIL |
Troy Cobbley
|
|
|
Per Brian the fire alarm system has not been pre tested, there are multiple problems and the entire system needs to be tested from the beginning.
|
Issue and Print Permit | | | 3/14/2007 | | DONE |
|
|
|
|
Alarm Plan Check | 3/12/2007 | | 3/12/2007 | | PASS |
|
|
|
Fire Alarm Review 3rd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/12/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 3/12/2007 | | 3/12/2007 | | DONE |
|
|
|
|
Telephone call | | | 3/12/2007 | | |
|
|
|
call to keith olstrom, permit ready to p/u, fees $314.85
|
Permit Ready to Issue | | | 3/12/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 11/20/2006 | | 3/12/2007 | | PASS |
|
|
|
3/12/2007 13:58:13 MWT - activity updated through activity FIRA22 from case FIR06-00918.
|
Alarm Plan Check | 2/15/2007 | | 2/15/2007 | | FAIL |
|
|
|
Fire Alarm Review 2nd
|
Telephone call | | | 2/15/2007 | | DONE |
|
|
|
call to keith olstrom, left msg on ans mach. plans need to be resubmitted.
|
Miscellaneous action | | | 2/15/2007 | | |
|
|
|
Faxed copy of review to Keith Olstrum Vanguard Protection ###-####
|
Plan resubmittals received | | | 2/13/2007 | | |
|
|
|
|
Alarm Plan Check | 12/4/2006 | | 12/4/2006 | | FAIL |
|
|
|
Fire Alarm Review 1st
|
Miscellaneous action | | | 12/4/2006 | | |
|
|
|
Had meeting with the fire alarm vendor/designer. I told Keith that I have concerns about his design qualifications. I presented to him the deficiencies on this simple fire alarm system and Keith agreed that he continues to make mistake after mistake. His level of NICET qualification is level 1 (Not sufficient for fire alarm system design) I requested that he submit to me his factory training credentials due to he has no other design qualifications.
|
Telephone call | | | 12/4/2006 | | DONE |
|
|
|
t/c w keith olstrom at Vanguard Protection Group ###-#### - permit needs to be picked up and resubmitted - no fees
|
Case Summary | | | 11/20/2006 | | DONE |
|
|
|
|
Application received | | | 11/20/2006 | | |
|
|
|
|