INSP-Final Inspection | 1/24/2007 | 1/24/2007 | 1/24/2007 | A | PASS |
Forrest France
|
|
|
Corrections have been verified for completion, final alarm inspeciton passed.
|
INSP-Final Inspection | 1/23/2007 | 1/23/2007 | 1/23/2007 | P | FAIL |
Troy Cobbley
|
|
|
The fire alarm panel's display showed abunch of gibberish when testing phone line #2 and would not clear until all power had been dumped. Per Matt with Silent Knight technical support the panel should be replaced. The serial numbers on the existing panel mother bord are SN38273. These should change with a new board. Entire system will need to be tested.
|
INSP-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 | P | FAIL |
Forrest France
|
|
|
The PIV tamper switch is not correctly installed or adjusted, also lacking NFPA 72 record of inspeciton and testing to be completed (per review comments) prior scheduling final field acceptance test.
|