INSP-Final Inspection | 8/8/2007 | 8/9/2007 | 8/9/2007 | P | PASS |
Forrest France
|
|
|
Final fire alarm inspection passed, permit finaled.
|
INSP-Final Inspection | 8/3/2007 | 8/3/2007 | 8/3/2007 | P | DEFR |
Forrest France
|
|
|
Inspection rescheduled per conversation with contractor.
|
INSP-Final Inspection | 7/31/2007 | 8/3/2007 | 8/3/2007 | A | CANC |
Forrest France
|
|
|
Final bay 10 Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
|
INSP-Alarm Testing | 7/26/2007 | 7/31/2007 | 7/31/2007 | A | PASS |
Forrest France
|
|
|
Fire alarm modifications passed field testing.
|
INSP-Final Inspection | 7/26/2007 | 8/2/2007 | 7/31/2007 | A | CANC |
Forrest France
|
|
|
life safety Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
|
Issue and Print Permit | | | 7/18/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/17/2007 | | |
|
|
|
Ready for Issue
|
Alarm Plan Check | 7/12/2007 | | 7/12/2007 | | PASS |
|
|
|
Fire Alarm Resubmittal Plan Modification Done by Mike Timmerman 7/12/2007 Approved as Noted on Revision 2 Fire Alarm Plans.
|
Plan assigned to (SAM) | 6/8/2007 | | 6/27/2007 | | PASS |
|
|
|
6/27/2007 13:18:42 JCM - activity updated through activity FIRA22 from case FIR06-00959.
|
Alarm Plan Check | 5/31/2007 | | 6/8/2007 | | FAIL |
|
|
|
Plan modification review: The followng comments were emailed to Paul Marcolina:
Paul,
To complete my review of these two permits, I will need the following information:
1. Because the previous F1 areas are being converted to H5, I need to see on the Building plans, the new boundaries of the H5 area.
2. I will need a Hazardous Material Summary/Classification/analysis of the entire H5 area, verifying that the total Haz Mat quantities located within the new H5 envelope are within allowable limits per IFC 1804; and a Haz Mat Classification/analysis verifying quantities at workstations within the proposed new H5 areas are within the allowable quantities per 1805.2.1.
3. The FA plans need to be revised to show the new boundaries of the entire H5 area and also show sufficient area surrounding the proposed new H5 spaces to confirm that:
A. manual pull stations are provided and spaced as required by 1803.11 and 907.4.1.
B. the emergency alarm system initiating devices and notification appliances are provided as required by 1803.12 and 908.2, including outside the H5 exits as required by 2704.9 and as applicable per 2705.4.4.
3. The title sheet FA0 should be revised to reflect the new occupancy and all appropriate alarm systems.
Thanks,
Sam
|
FIR-Aging Inspection | 6/6/2007 | 6/6/2007 | 6/7/2007 | | DEFR |
Forrest France
|
|
|
|
Plan resubmittals received | | | 5/31/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/27/2006 | | DONE |
|
|
|
|
Alarm Plan Check | 12/22/2006 | | 12/22/2006 | | PASS |
|
|
|
Onsite review, passed subject to annotations.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/22/2006 | | DONE |
|
|
|
|
Application received | | | 11/22/2006 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|