Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR06-00934
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project Name 
Customer NumberC9894
ePlanReview 
Description
Fire Alarm System: C9894 B2 F1A Remodel YA and Smock Room for Photo Bay 10 - Remove and install new fire alarm devices as required.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/8/20078/9/20078/9/2007PPASS
DetailsForrest France
Final fire alarm inspection passed, permit finaled.
INSP-Final Inspection8/3/20078/3/20078/3/2007PDEFR
DetailsForrest France
Inspection rescheduled per conversation with contractor.
INSP-Final Inspection7/31/20078/3/20078/3/2007ACANC
DetailsForrest France
Final bay 10 Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
INSP-Alarm Testing7/26/20077/31/20077/31/2007APASS
DetailsForrest France
Fire alarm modifications passed field testing.
INSP-Final Inspection7/26/20078/2/20077/31/2007ACANC
DetailsForrest France
life safety Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
Issue and Print Permit  7/18/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  7/17/2007  
Ready for Issue
Alarm Plan Check7/12/2007 7/12/2007 PASS
Fire Alarm Resubmittal Plan Modification Done by Mike Timmerman 7/12/2007 Approved as Noted on Revision 2 Fire Alarm Plans.
Plan assigned to (SAM)6/8/2007 6/27/2007 PASS
6/27/2007 13:18:42 JCM - activity updated through activity FIRA22 from case FIR06-00959.
Alarm Plan Check5/31/2007 6/8/2007 FAIL
Plan modification review: The followng comments were emailed to Paul Marcolina:
Paul,
To complete my review of these two permits, I will need the following information:
1. Because the previous F1 areas are being converted to H5, I need to see on the Building plans, the new boundaries of the H5 area.
2. I will need a Hazardous Material Summary/Classification/analysis of the entire H5 area, verifying that the total Haz Mat quantities located within the new H5 envelope are within allowable limits per IFC 1804; and a Haz Mat Classification/analysis verifying quantities at workstations within the proposed new H5 areas are within the allowable quantities per 1805.2.1.
3. The FA plans need to be revised to show the new boundaries of the entire H5 area and also show sufficient area surrounding the proposed new H5 spaces to confirm that:
A. manual pull stations are provided and spaced as required by 1803.11 and 907.4.1.
B. the emergency alarm system initiating devices and notification appliances are provided as required by 1803.12 and 908.2, including outside the H5 exits as required by 2704.9 and as applicable per 2705.4.4.
3. The title sheet FA0 should be revised to reflect the new occupancy and all appropriate alarm systems.
Thanks,
Sam
FIR-Aging Inspection6/6/20076/6/20076/7/2007 DEFR
DetailsForrest France
Plan resubmittals received  5/31/2007 DONE
Issue and Print Permit  12/27/2006 DONE
Alarm Plan Check12/22/2006 12/22/2006 PASS
Onsite review, passed subject to annotations.
PLANS/APPL TAKEN TO FRONT DESK  12/22/2006 DONE
Application received  11/22/2006 DONE
This permit was created on the web by Paul Marcolina