Permit NumberFIR06-00938
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1405 N MILWAUKEE ST
Project NameFAIRVIEW/MILWAUKEE PLAZA
Customer Number 
ePlanReview 
Description
The Permitted Work Scope:The fire sprinkler scope of work includes relocating the existing anti-freeze loop assembly + or - 5'-0" north to accommodate a new non-bearing wall layout. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. This permit is attached to BLD06-02704. When tenant work affects fire sprinkler protection outside the permitted work area. The affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The "Riser" and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/31/20071/31/20071/31/2007PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/29/20071/29/20071/30/2007PFAIL
DetailsTroy Cobbley
Can't final until tile is installed. Sprinkler piping can be covered. Insulation has been repaired.
INSP-Final Inspection1/26/20071/26/20071/26/2007PCANC
DetailsTroy Cobbley
Duplicate inspection
INSP-Sprinkler Rough-in/Hydro1/25/20071/26/20071/26/2007AFAIL
DetailsTroy Cobbley
All corrections have been made except there are still problems with the insulation falling and blocking the upright sprinkler heads. Do not cover sprinklers.
INSP-Sprinkler Rough-in1/22/20071/22/20071/22/2007PFAIL
DetailsTroy Cobbley
See the city approved plans for the corrects required as marked in red. This includes the repairing of the insulation which is blocking the upright sprinklersPiping is not to be covered.
INSP-Conference1/17/20071/18/20071/18/2007ADONE
DetailsTroy Cobbley
Inspection was for the hanging obstruction in the open area. I told Matt that the 18" clearance probably does not apply and that there is an obstruction rule in NFPA 13 that would.
Permit Ready to Issue  12/6/2006 DONE
Inspection Record Card- Fire12/6/2006 12/6/2006 DONE
Inspection Record Card- Fire12/6/2006 12/6/2006 DONE
Telephone call  12/6/2006 DONE
tlk to brad bettencourt that permit and fees are ready to be picked up
Issue and Print Permit  12/6/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/5/2006 DONE
Sprinkler Plan Check11/27/2006 12/4/2006 PASS
Reviewed by B. Johnson. No heads involved, no contract amount; apply minimum permit charge.
Application received  11/27/2006  
Per Scott A. ok to take in plans
Pending Assignment by SAM11/27/2006