Information based on query as of Saturday, August 17, 2024.
Permit Information
Permit NumberFIR06-00941
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3823 N 36TH ST
Project NameGarden Center Shell
Customer Number 
ePlanReview 
Description
Revised Scope of Work: 02/23/07 Plans & calculations were resubmitted as a result of the field inspectors request due to additional heads being added to remote area #2. Plans & calculations are approved as submitted and do not appear to adversely affect the operation of the system as designed.
Original Scope of Work:
Garden Center (Shell & Core) - To construct a new 12,000 square foot, one story, steel frame retail and restaurant shell building and related site improvements. This building will contain a future 3,480 square foot restaurant, a 600 square foot mechanical room and a future 7,920 square foot retail garden store. The garden store tenant improvement is being constructed concurrently with this shell building under building permit BLD06-00454. The Under Ground supply was installed under permit FIR06-00591, consisting of a 140’-0” run of 6” C-900 beginning at a new tapping tee provided by others. The overhead fire sprinkler protection will consist of a shell only, wet pipe system through out the entire structure. The system supply will be boosted be a 500 gpm @ 80 psi inline booster pump, to be located in the Mechanical room. The system supply will be controlled from a Wall PI valve outside the Mechanical room.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-00453.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/27/20074/27/20074/27/2007PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection4/27/20074/27/20074/27/2007PFAIL
DetailsTroy Cobbley
Per Brian the tamper switchs need adjusting so that a correct signal is given at the fire alarm panel
INSP-Final Inspection4/25/20074/26/20074/27/2007AFAIL
DetailsTroy Cobbley
Per Brian the tamper switchs need adjusting so that a correct signal is given at the fire alarm panel
INSP-Sprinkler Rough-in/Hydro4/25/20074/26/20074/27/2007APASS
DetailsTroy Cobbley
The hydro on the fire pump loop passed. It took two times per Brian.
INSP-Sprinkler Rough-in/Hydro4/27/20074/27/20074/27/2007PCANC
DetailsTroy Cobbley
Jonathan is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in4/19/20074/23/20074/23/2007PPASS
DetailsTroy Cobbley
The fire pump acceptance test passed. Turning the first automatic startup the fire pump experienced phase loss but was not repeated.
INSP-Sprinkler Rough-in/Hydro4/16/20074/17/20074/17/2007APASS
DetailsTroy Cobbley
The overhead hydro test passed of all piping from the riser on. The fire pump bypass and fdc still need testing
Issue and Print Permit  2/27/2007 DONE
Inspection Record Card- Fire2/26/2007 2/26/2007 DONE
Telephone call  2/26/2007  
lft ms for lily that pemit is ready to be picked up and no fees
Permit Ready to Issue  2/26/2007 DONE
Case Summary  2/26/2007 DONE
Sprinkler Plan Check2/23/2007 2/26/2007 PASS
*As built Plans & Calculations are approved 02/23/2007
PLANS/APPL TAKEN TO FRONT DESK  2/26/2007 DONE
(F) Reprint permit  12/18/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/6/2006 DONE
Override - Parcel Holds  12/6/2006  
Inspection Record Card- Fire12/6/2006 12/6/2006 DONE
Telephone call  12/6/2006 DONE
t/c w lilly at shilo ###-####- permit ready and fees given ($617.40)
Override - Parcel Holds  12/6/2006  
Override - Parcel Holds  12/6/2006  
Permit Ready to Issue  12/6/2006 DONE
Override - Parcel Holds  12/6/2006  
Override - Parcel Holds  12/6/2006  
Issue and Print Permit  12/6/2006  
Sprinkler Plan Check11/27/2006 12/5/2006 PASS
Reviewed by B. Johnson; approved with conditions.
Case Summary  11/27/2006 DONE
Application received  11/27/2006  
Pending Assignment by SAM11/27/2006    
Inspection Record Card- Fire2/26/2007