INSP-Final Inspection | 2/5/2007 | 2/7/2007 | 2/7/2007 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Alarm Testing | 1/25/2007 | 1/29/2007 | 1/30/2007 | P | FAIL |
Forrest France
|
|
|
SD at the elevator lobby failed to recall the car, need to test the hood suppression system interconnection, provide access for testing of the PIV tamper, noted one duct detector in need of revision of sample and vent tube orientation (repaired while on site), remove the duct insulation liner at the vent tube on the remaining duct detectors. The panel, manual pull, SD at panel, waterflow and sprinkler main control tested okay. Also need verification of signals recieved as discussed.
|
Issue and Print Permit | | | 12/20/2006 | | DONE |
|
|
|
|
Alarm Plan Check | 12/19/2006 | | 12/19/2006 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/19/2006 | | |
|
|
|
Ready for Issue: Double Permit Fee, Work Started before plan review was complete.
|
Inspection Record Card- Fire | 12/19/2006 | | 12/19/2006 | | DONE |
|
|
|
|
Telephone call | | | 12/19/2006 | | DONE |
|
|
|
t/c w matt at crane alarm ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 12/19/2006 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 11/27/2006 | | 12/19/2006 | | PASS |
|
|
|
12/19/2006 12:09:55 MWT - activity updated through activity FIRA22 from case FIR06-00942.
|
Plan resubmittals received | | | 12/15/2006 | | |
|
|
|
|
Miscellaneous action | | | 12/8/2006 | | DONE |
|
|
|
picked up plans, resubmittals required
|
Telephone call | | | 12/7/2006 | | DONE |
|
|
|
t/c w teresa at crane alarm service ###-#### - permit ready to be picked up and re-submitted
|
Alarm Plan Check | 12/6/2006 | | 12/6/2006 | | FAIL |
|
|
|
Fire Alarm Review 1st review
|
Miscellaneous action | | | 12/6/2006 | | |
|
|
|
Faxed Fire Alarm System Review to Crane Alarm and Farren Engineering.
|
Telephone call | | | 12/6/2006 | | |
|
|
|
Talked to Brent Crane. Brent said that they wanted to remove the existing fire alarm system and replace it with a new one because they cannot work on Notifier Systems. I told him that was an absolute no-no. With out permission from the Fire Marshal.
|
Case Summary | | | 11/27/2006 | | DONE |
|
|
|
|
Application received | | | 11/27/2006 | | |
|
|
|
|