Permit Information
Permit NumberFIR06-00952
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1249 S VINNELL WAY
Project NameBLM BLDG
Customer Number 
ePlanReview 
Description
Fist Floor TI. This building is fire sprinklered for area increase. To expand and remodel the reception and customer service area of an existing office tenant space. After the expansion, the customer area will have a floor area of about 1,485 square feet. The sprinkler scope of work includes adding 16 standard response down heads to accommodate the new wall and ceiling layout. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. This permit is attached to BLD06-02638.
When tenant work affects fire sprinkler protection outside the permitted work area. The affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The "Riser" and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/21/20072/22/20072/22/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection2/21/20072/21/20072/21/2007PPART
DetailsTroy Cobbley
Sprinkler piping is ok to cover but one head as marked on the plans was modified but is piped from an outlet that already has a drop on it. This head is shown on the plans as being piped from a mechanical tee. As per policy the two heads from a single 1" outlet is not allowed unless certain conditions have been met. Prove conditions or install as per the plans.
Issue and Print Permit  12/11/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/8/2006 DONE
Telephone call  12/8/2006 DONE
lft vm for brodie ###-#### that permit and fees are ready to be picked up
Inspection Record Card- Fire12/8/2006 12/8/2006 DONE
Permit Ready to Issue  12/8/2006 DONE
Sprinkler Plan Check12/1/2006 12/6/2006 PASS
Application received  11/30/2006  
Pending Assignment by SAM11/30/2006