Permit Information
Permit NumberFIR06-00955
StatusFinaled
Name WESTERN STATES FIRE PROTECTION
Site Address 1757 N HAMPTON RD
Project Name 
Customer Number 
ePlanReview 
Description
The data has been moved to a Word document attached to this case.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/8/20073/8/20073/8/2007PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro3/7/20073/8/20073/8/2007APASS
DetailsTroy Cobbley
Underground hydro passed. Calculation sticker and flexible couplings installed.
INSP-Final Inspection3/6/20073/7/20073/7/2007PFAIL
DetailsTroy Cobbley
provide flexible couplings at the top and bottom of the riser and provide hydraulic sticker for the rise
INSP-Final Inspection3/5/20073/6/20073/6/2007PCANC
DetailsTroy Cobbley
waiting on fire alarm
INSP-Sprinkler Rough-in/Hydro3/1/20073/1/20073/2/2007PPASS
DetailsTroy Cobbley
Above ground hydro test passed. This includes the anti-freeze loop.
INSP-Supply line flush2/15/20072/16/20072/16/2007APASS
DetailsTroy Cobbley
Underground flush passed.
INSP-Sprinkler Rough-in1/29/20071/30/20071/30/2007APASS
DetailsTroy Cobbley
Underground piping is ok to cover
Telephone call  1/24/2007 DONE
Telcon from "Mick" of Western Fire Protection-regarding the lack of prescribed depth of bury of a section of UG. He proposed two alt's: covering pipe with foam and putting a speed bump over the trench, instead of adding 4 el's to drop the pipe/trench depth to prescribed depth. I indicated we would consider either of his proposed alt's if the design were prepared and stamped, with supporting calc's showing the alt design would have the equivalent insulating value as the prescribed method. He will investigate the 3 options further before making a decision.
INSP-Supply line flush1/22/20071/22/20071/22/2007PFAIL
DetailsTroy Cobbley
This was for an underground inspection.The underground supply piping is not buried below 4'-6" as required. Top of pipe is at 3'-10"
INSP-Sprinkler Rough-in12/20/200612/21/200612/21/2006APART
DetailsTroy Cobbley
Sprinkler piping is ok to cover but some items have not been corrected. See city approved plans for the redlined items.
INSP-Sprinkler Rough-in12/15/200612/18/200612/18/2006PFAIL
DetailsTroy Cobbley
Pipe sizes as shown on the plans, in the locations marked, do not match the piping as installed. Pipe needs to be changed or these changes need to be proven with revised hydraulic calculations when the as-builts are resubmitted as per the review comments. There are other deficiencies also marked on the plans. Piping is not to be covered.
Inspection Record Card- Fire12/15/2006 12/15/2006 DONE
Permit Ready to Issue  12/15/2006 DONE
Telephone call  12/15/2006 DONE
tlk to mick in boise and let him that permit and fees are ready to be picked up
Issue and Print Permit  12/15/2006 DONE
Sprinkler Plan Check12/1/2006 12/14/2006 PASS
Plan review done by Bryan Johnson
PLANS/APPL TAKEN TO FRONT DESK  12/14/2006 DONE
Application received  12/1/2006  
Pending Assignment by SAM12/1/2006