Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR06-00956
StatusFinaled
Name FIRE PROTECTION SYSTEMS LLC
Site Address 5850 N FIVE MILE RD
Project NameBONAVENTURE PLACE
Customer Number 
ePlanReview 
Description
Locate the FDC remotely from the bldg. The new location will be in close proximity to the Post Indicator Valve as originally approved. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire “Inspection Card” are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD06-01069.Original Scope of Work: Underground & Overhead
Install underground services beginning and the property line, run 6” PVC out and rise up into a common riser room serving three separate structures. The under ground supply will be controlled from a Post indicating valve. Each of the three structures is to be protected through out. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-01069, BLD06-00579 & BLD06-00582.
Revised Scope of Work: Overhead Only
Add sprinkler coverage at the dormer overbuilds in the attics of bldg. C & D. Add sprinkler coverage above the kitchen area in bldg. B. A total of 33 new heads were added as a result of these changes. All four of the structures are to be protected through out. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief09/20/07 Revised Scope of Work: Overhead Only
These plans were resubmitted due to changes made in the field during construction. The previously approved plans listed the Viking Freedom heads with a 5.5 k-factor, with a minimum starting pressure for the approved spacing of 16’ x 16’ was 21.66 psi. The designer substituted a Reliable model F1-Res-58. The characteristics of the Reliable head are a 5.8 k-factor, with a minimum starting pressure for the approved spacing of 16’ x 16’ was 19.48 psi. The substitution affected Remote areas 3, 4 & 5. The result is that the substitutions benefited the system by operating at a lower pressure by 2.18 psi.09/20/07 Revised Scope of Work: Overhead Only
These plans were resubmitted due to changes made in the field during construction. The previously approved plans listed the Viking Freedom heads with a 5.5 k-factor, with a minimum starting pressure for the approved spacing of 16’ x 16’ was 21.66 psi. The designer substituted a Reliable model F1-Res-58. The characteristics of the Reliable head are a 5.8 k-factor, with a minimum starting pressure for the approved spacing of 16’ x 16’ was 19.48 psi. The substitution affected Remote areas 3, 4 & 5. The result is that the substitutions benefited the system by operating at a lower pressure by 2.18 psi.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/2/200710/3/200710/3/2007APASS
DetailsTroy Cobbley
Permit finaled
Issue permit  9/25/2007  
INSP-Final Inspection9/21/20079/24/20079/24/2007ACANC
DetailsTroy Cobbley
Cancelled due to alarm panel problems.
PLANS/APPL TAKEN TO FRONT DESK  9/24/2007 DONE
Inspection Record Card- Fire9/24/2007 9/24/2007 DONE
Telephone call  9/24/2007 DONE
tlk to dennis skiner ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  9/24/2007 DONE
INSP-Final Inspection9/20/20079/21/20079/21/2007AFAIL
DetailsTroy Cobbley
Todays inspection covered reinspecting the blocked sprinkler heads through out the building. The only areas not inspected for blockage are the 1st and 2nd floors of D wing.
INSP-Final Inspection9/20/20079/20/20079/20/2007PCANC
DetailsTroy Cobbley
Overbooked with Micron plan review.
Sprinkler Plan Check9/5/2007 9/20/2007 PASS
As--built plans are approved 09/20/2007 by Bryan Johnson
INSP-Final Inspection9/17/20079/19/20079/19/2007PCANC
DetailsTroy Cobbley
gilbert was not ready for inspection when I was there with Mike and Ken.
INSP-Final Inspection9/5/20079/6/20079/6/2007AFAIL
DetailsTroy Cobbley
I inspected the second floor wings D, C and B. As with the previous inspection many pendants are blocked and the electrical room is missing coverage. I stopped the inspection until all of blocked heads have been fixed.
INSP-Final Inspection9/4/20079/5/20079/5/2007AFAIL
DetailsTroy Cobbley
The remaining 3rd floor areas were inspected. The same obstructions as noted yesterday occur in the other third floor areas. There was no access into room 397. A canopy was missing from the bathroom pendant in room 374 and no sprinkler coverage was provided in the corridor electrical closet on the third floor C wing. The items from the previous correction notice still need addressed.
Plan resubmittals received  9/5/2007  
INSP-Final Inspection8/31/20079/4/20079/4/2007AFAIL
DetailsTroy Cobbley
The final inspecton for the third floor of A wing was started today. I found that instead of viking pendants being installed reliable pendants had been installed. Also many of the light fixtures are blocking the pendant heads in the laundry/utility romms and in the main corridor.
INSP-Conference8/27/20078/27/20078/27/2007PDONE
DetailsTroy Cobbley
I spoke to Katie about the occupancy load signs and their locations.
Inspection Record Card- Fire6/19/2007 7/2/2007  
Plan resubmittals received  6/19/2007  
PLANS/APPL TAKEN TO FRONT DESK  3/8/2007 DONE
Telephone call  3/8/2007 DONE
tlk to fire protection ###-#### that permit is ready to be picked up
Permit Ready to Issue  3/8/2007 DONE
Inspection Record Card- Fire3/8/2007 3/8/2007 DONE
(F) Reprint permit  3/8/2007 DONE
CHANGE STATUS TO (ISS)  3/8/2007 DONE
Sprinkler Plan Check3/6/2007 3/7/2007 PASS
Plans are approved per attached findings per Bryan Johnson
Plan resubmittals received  3/6/2007  
plans sent directly to B. Johnson by contractor; relocation of proposed wall FDC to a yard area.
INSP-Sprinkler Rough-in2/20/20072/21/20072/22/2007APASS
DetailsTroy Cobbley
Inspection was for building C. Rough to cover for third floor passed, Attic/dry system pipe passed, first and second floor main piping EQ restraints and hanger assemblies passed, first and second floor rough to cover passed. The FDC location is in question. Brian asked the general/Dale to supply PDS with a new proposed layout for review.
INSP-Sprinkler Rough-in/Hydro1/31/20072/2/20072/2/2007APASS
DetailsTroy Cobbley
hydro tests for 1st, 2nd and 3rd floors of the north wing passed. These were witnessed by the superintendant dale shuart
Issue and Print Permit  1/24/2007 DONE
Case Summary  1/19/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  1/19/2007 PASS
Inspection Record Card- Fire1/19/2007 1/19/2007 DONE
Permit Ready to Issue  1/19/2007 DONE
Telephone call  1/19/2007 DONE
tlk to dennis skinner ###-#### that permit and fees are ready to be picked up
Sprinkler Plan Check1/9/2007 1/16/2007 PASS
Plan review by Bryan Johnson
Plan resubmittals received  1/9/2007  
Sprinkler Plan Check12/18/2006 12/20/2006 FAIL
denied 12/18/2006 plans retained by Bryan Johnson
Plan resubmittals received  12/4/2006  
Received page 1 of 16 and 4 sets of hydraulic calculations; taken to Sam Rogers
Application received  12/1/2006  
Pending Assignment by SAM12/1/2006