Permit Information
Permit NumberFIR06-00957
StatusFinaled
Name FIRE PROTECTION SYSTEMS LLC
Site Address 5850 N FIVE MILE RD
Project NameBONAVENTURE PLACE
Customer Number 
ePlanReview 
Description
Install underground services beginning and the property line, run 6” PVC out and rise up into a common riser room serving three separate structures. (Bldg. A, B, C & D) The under ground supply will be controlled from a Post indicating valve. Building D is protected through out above and below the ceiling. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-01069, BLD06-00579 & BLD06-00582.Original Scope of Work: Underground & Overhead
Install underground services beginning and the property line, run 6” PVC out and rise up into a common riser room serving three separate structures. The under ground supply will be controlled from a Post indicating valve. Each of the three structures is to be protected through out. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-01069, BLD06-00579 & BLD06-00582.
Revised Scope of Work: Overhead Only
Add sprinkler coverage at the dormer overbuilds in the attics of bldg. C & D. Add sprinkler coverage above the kitchen area in bldg. B. A total of 33 new heads were added as a result of these changes. All four of the structures are to be protected through out. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/2/200710/3/200710/3/2007APASS
DetailsTroy Cobbley
permit finaled
CHANGE STATUS TO (ISS)  9/25/2007  
already issued
INSP-Final Inspection9/21/20079/24/20079/24/2007ACANC
DetailsTroy Cobbley
Cancelled due to alarm panel problems.
PLANS/APPL TAKEN TO FRONT DESK  9/24/2007 DONE
Inspection Record Card- Fire9/24/2007 9/24/2007 DONE
Telephone call  9/24/2007 DONE
tlk to dennis skiner ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  9/24/2007 DONE
INSP-Final Inspection9/20/20079/21/20079/21/2007AFAIL
DetailsTroy Cobbley
Todays inspection covered reinspecting the blocked sprinkler heads through out the building. The only areas not inspected for blockage are the 1st and 2nd floors of D wing.
INSP-Final Inspection9/20/20079/20/20079/20/2007PCANC
DetailsTroy Cobbley
Overbooked with Micron plan review.
Sprinkler Plan Check9/5/2007 9/20/2007 PASS
As---built Plans are approved 09/20/2007 by Bryan Johnson
INSP-Final Inspection9/17/20079/18/20079/18/2007PFAIL
DetailsTroy Cobbley
Todays inspection covered the modified sprinkler heads in "A" wing 1st, 2nd and 3rd floors. They all look good except for one head was missed in the southwest third floor stairwell ceiling and in the common electrical room that is on all floors.
INSP-Final Inspection9/5/20079/6/20079/6/2007AFAIL
DetailsTroy Cobbley
I inspected the second floor wings D, C and B. As with the previous inspection many pendants are blocked and the electrical room is missing coverage. I stopped the inspection until all of blocked heads have been fixed.
INSP-Final Inspection9/4/20079/5/20079/5/2007AFAIL
DetailsTroy Cobbley
The remaining 3rd floor areas were inspected. The same obstructions as noted yesterday occur in the other third floor areas. There was no access into room 397. A canopy was missing from the bathroom pendant in room 374 and no sprinkler coverage was provided in the corridor electrical closet on the third floor C wing. The items from the previous correction notice still need addressed.
Plan resubmittals received  9/5/2007  
INSP-Final Inspection8/31/20079/4/20079/4/2007AFAIL
DetailsTroy Cobbley
The final inspecton for the third floor of A wing was started today. I found that instead of viking pendants being installed reliable pendants had been installed. Also many of the light fixtures are blocking the pendant heads in the laundry/utility romms and in the main corridor.
INSP-Sprinkler Rough-in6/25/20076/26/20076/27/2007PPASS
DetailsTroy Cobbley
I inspected Bldg. D attic piping today. There were a few problems with bracing, the problems were corrected by the end of the inspection. I also witnessed the hydro test for the attic piping and second floor of the same bldg. The hydro went fine.
INSP-Sprinkler Rough-in/Hydro6/22/20076/25/20076/25/2007ACANC
DetailsTroy Cobbley
gilbert; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
Plan resubmittals received  6/19/2007  
INSP-Sprinkler Rough-in/Hydro5/29/20075/31/20075/31/2007APASS
DetailsTroy Cobbley
The second floor of building D rough to cover is passed as well as the second floor hydro test
INSP-Sprinkler Rough-in/Hydro5/18/20075/21/20075/21/2007PPASS
DetailsTroy Cobbley
The first floor of area "D" is ok to cover except for the areas where the attic system needs to be installed. Per the general contractor there are support issues with the light weight trusses that are being worked out with the structural engineer.
INSP-Sprinkler Rough-in2/7/20072/9/20072/9/2007ACANC
DetailsTroy Cobbley
Inspection performed yesterday by Brian Johnson
INSP-Sprinkler Rough-in2/7/20072/8/20072/8/2007APART
DetailsTroy Cobbley
First and second floors of the C wing are ok to cover. Third floor can not be covered yet. See city approved plans for the corrections required.
INSP-Sprinkler Rough-in2/5/20072/6/20072/6/2007APART
DetailsTroy Cobbley
The second floor of C wing will be ok to cover when the insulation is installed between the walls and the drop downs to the dry sidewalls. Also one pendant is overspaced as marked on the plans. C wing attic dry system 200 lb hydro test passed.
INSP-Sprinkler Rough-in/Hydro2/2/20072/5/20072/5/2007APASS
DetailsTroy Cobbley
First floor of the C wing rough-in piping was completed today. Contractor needs to provide verification from truss manufacturer for the mounting of the eq bracing and the hanging of the 3" main.
Issue and Print Permit  1/24/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  1/19/2007 PASS
Inspection Record Card- Fire1/19/2007 1/19/2007 DONE
Permit Ready to Issue  1/19/2007 DONE
Telephone call  1/19/2007 DONE
tlk to dennis skinner ###-#### that permit and fees are ready to be picked up
Sprinkler Plan Check1/9/2007 1/16/2007 PASS
Plan review by Bryan Johnson
Plan resubmittals received  1/9/2007  
Sprinkler Plan Check12/4/2006 12/18/2006 FAIL
plans retained by Bryan Johnson
Plan resubmittals received  12/4/2006  
Received page 1 of 16 and 4 sets of hydraulic calculations; taken to Sam Rogers
Application received  12/1/2006  
Pending Assignment by SAM12/1/2006    
Inspection Record Card- Fire9/24/2007