(F) Reprint permit | | | 4/20/2007 | | |
|
|
|
|
INSP-Final Inspection | 1/15/2007 | 1/16/2007 | 1/17/2007 | A | PASS |
Forrest France
|
|
|
Field corrections are complete, fire alarm permit finaled.
|
Miscellaneous action | | | 1/17/2007 | | |
|
|
|
Received plans additional info; put in Forrest's box
|
INSP-Final Inspection | 1/10/2007 | 1/11/2007 | 1/11/2007 | A | FAIL |
Forrest France
|
|
|
Existing strobes at some locations are mounted below min. height allowed AFF, strobe notification devices in some areas are not in synchronization as required, need to lower two pull stations, a/v's at two locations are blocked by doors when in the open position, a/v's are overspaced at the SW corner, will check new nac batteries, modifications, as-built plans, and signal verification at next inspection.
|
Issue and Print Permit | | | 12/13/2006 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 12/4/2006 | | 12/12/2006 | | PASS |
|
|
|
12/12/2006 15:32:02 MWT - activity updated through activity FIRA22 from case FIR06-00963.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/12/2006 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 12/12/2006 | | 12/12/2006 | | DONE |
|
|
|
|
Telephone call | | | 12/12/2006 | | DONE |
|
|
|
t/c w Jodi Spencer at Mountain Alarm ###-#### - permit ready and fees given ($150.00)
|
Permit Ready to Issue | | | 12/12/2006 | | DONE |
|
|
|
|
Alarm Plan Check | 12/11/2006 | | 12/11/2006 | | PASS |
|
|
|
Fire Alarm Review
|
Telephone call | | | 12/11/2006 | | PEND |
|
|
|
Called Alarm Vendor, Lynde (Mountain Alarm) Requested alarm system matrix to complete the issue of this fire alarm review. Two notification appliances were also noted as requiring modification to the design. This information was noted in general comments in the fire alarm review. This was also to be relayed to Designer Stephanie Cobbley by the alarm company. Issue of this permit is pending me receiving the alarm matrix.
|
Miscellaneous action | | | 12/11/2006 | | |
|
|
|
Waiting on Alarm Matrix from Fire Alarm Vendor. (Mountain Alarm)
|
Case Summary | | | 12/4/2006 | | DONE |
|
|
|
|
Application received | | | 12/4/2006 | | |
|
|
|
|