Permit Information
Permit NumberFIR06-00986
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 2211 E WARM SPRINGS AVE
Project NameFALLINGBROOK CONDOS
Customer Number 
ePlanReview 
Description
To construct a new 13,676 sq. ft., two story, ten unit, apartment building. An NFPA 13R fire sprinkler system is required in each unit. NOTE: Each unit is over 800 sq. ft. Each unit is separated from adjoining unit by a 1-hour fire partition extending from top of foundation to tight against the bottom of the roof deck. This structure will be fire sprinklered through out the living space. System shall be equipped with an alarm initiating device connected to an alarm system and an outside annunciating devise. All fire sprinkler work and related, which includes dual service underground water supply, the system backflow prevention device (provided by others), shall be per NFPA 13R, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD06-01992.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/13/20082/13/20082/13/2008PPASS
DetailsForrest France
C/N items are finished, fire sprinkler permit finaled.
INSP-Final Inspection2/11/20082/12/20082/12/2008AFAIL
DetailsForrest France
Need to remove travel caps and install escutcheons at each sprinkler head in the mechanical closets per unit.
INSP-Final Inspection2/6/20082/7/20082/7/2008PFAIL
DetailsForrest France
Missing several items for final at the riser similar to the adjacent building #2. Not ready for final due to missing and defficient items.
INSP-Sprinkler Rough-in/Hydro5/11/20075/14/20075/14/2007PPART
DetailsForrest France
OH hydrostatic test for the west building (bld#1) passed.
INSP-Sprinkler Rough-in/Hydro3/30/20074/3/20074/3/2007APART
DetailsForrest France
OH rough-in inspection completed for building one, noted some areas in need of correction prior to approval for cover including two heads too close to adjacent walls, heads at two locations that exceed min. spacing requirements, tenting at one head 2nd floor mech. closet is inadequate, need to provide proper coverage at the garage soffits above the water heaters.
INSP-Sprinkler Rough-in/Hydro1/24/20071/25/20071/25/2007APART
DetailsForrest France
UG supply line is approved for cover.
Issue and Print Permit  1/5/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/29/2006 DONE
Inspection Record Card- Fire12/29/2006 12/29/2006 DONE
Telephone call  12/29/2006 DONE
tlk to secretary ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  12/29/2006 DONE
Sprinkler Plan Check12/14/2006 12/27/2006 PASS
Plan review by Bryan Johnson
Application received  12/13/2006  
Pending Assignment by SAM12/13/2006