Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR06-01000
StatusFinaled
Name PEAK ALARM
Site Address 9288 W EMERALD ST
Project NameGE HARRIS LLC
Customer Number 
ePlanReview 
Description
This permit is to provide HVAC monitoring, audible visual notification and monitoring of a fire suppression control panel in a new tenant space in an existing building. Building permit # BLD06-02615 is to construct a 9,307 square foot telephone exchange tenant space within an existing 20,634 square foot building. Work is to include 1-hr fire barrier walls around a battery room control area, interior nonbearing walls, interior doors, 2 new exterior doors, a single user shower room accessible to the disabled, suspended ceilings, and interior finishes. In addition, two existing restrooms will be upgraded to be accessible to the disabled. A 2,377 square foot equipment enclosure will be constructed next to this building. A generator with fuel tanks and condensers for cooling will be installed within the enclosure. The enclosure will be surrounded by a chain link fence and will be open to the sky. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/1/20075/1/20075/1/2007PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection5/1/20075/1/20075/1/2007PPASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing3/22/20073/23/20073/23/2007APART
DetailsTroy Cobbley
A temporary occupancy was given with dave hannimans permission until items as noted by mike timmermans inspection have been corrected.
Issue permit  1/4/2007 DONE
Plan assigned to (Mike)12/21/2006 12/28/2006 PASS
12/28/2006 12:18:38 MWT - activity updated through activity FIRA22 from case FIR06-01000.
Alarm Plan Check12/28/2006 12/28/2006 PASS
Fire Alarm Review 1st
PLANS/APPL TAKEN TO FRONT DESK  12/28/2006  
Ready for Issue
Inspection Record Card- Fire12/28/2006 12/28/2006 DONE
Telephone call  12/28/2006 DONE
t/c w ben at peak alarm ###-#### - permit ready and fees given ($179.40)
Permit Ready to Issue  12/28/2006 DONE
Case Summary  12/21/2006  
Application received  12/21/2006  
Inspection3/23/20073/23/2007  PASS
Conducted fire alarm system inspection with Randy (Peak Alarm), Found a couple of notification appliances that required the candela settings to be increased. Also, the Duct Smoke Detectors were not installed because each unit serves separate areas and the units have ducted returns. (Non Plenum) The three HVAC roof top units are less than 2000 CFM. Alarm system notification appliance EOL voltage tested OK Batteries are two years old.

Signed temporary side of inspection card, consulted with Troy about the fact the existing FACP supervisory signals are latching and there is not supervisory LED on the FACP. The LCD display does describe the input as a supervisory input and the central station does receive the signal as a supervisory signal.