INSP-Final Inspection | 1/10/2007 | 1/10/2007 | 1/10/2007 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 1/9/2007 | 1/10/2007 | 1/10/2007 | A | PASS |
Forrest France
|
|
|
Required corrections have been completed, fire alarm permit finaled.
|
INSP-Final Inspection | 1/5/2007 | 1/8/2007 | 1/8/2007 | P | FAIL |
Forrest France
|
|
|
Phone line 2 trouble does not report, flow switch timing adjusted while on site, NFPA 72 record of inspection and testing should be completed prior to final field inspection.
|
Plan assigned to (Mike) | 12/26/2006 | | 12/29/2006 | | PASS |
|
|
|
12/29/2006 13:07:40 MWT - activity updated through activity FIRA22 from case FIR06-01012.
|
Miscellaneous action | | | 12/29/2006 | | |
|
|
|
Faxed copy of fire alarm review to Farren Engineering.
|
Telephone call | | | 12/29/2006 | | DONE |
|
|
|
t/c w helen - ###-#### - let her know the permit needed to be picked up and re-submitted
|
Plan resubmittals received | | | 12/29/2006 | | |
|
|
|
|
Alarm Plan Check | 12/29/2006 | | 12/29/2006 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/29/2006 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 12/29/2006 | | 12/29/2006 | | DONE |
|
|
|
|
Telephone call | | | 12/29/2006 | | DONE |
|
|
|
t/c w derek cooper - rrc contractors - ###-#### - permit ready and no fee
|
Permit Ready to Issue | | | 12/29/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/29/2006 | | DONE |
|
|
|
|
Telephone call | | | 12/28/2006 | | |
|
|
|
Called Jon Farren of Farren Engineering in regards to the sprinkler monitoring panel being located inside a persons residence and asked Jon to come up with an alternative location for the panel.
|
Case Summary | | | 12/26/2006 | | DONE |
|
|
|
|
Application received | | | 12/26/2006 | | |
|
|
|
|
Alarm Plan Check | 12/29/2006 | | | | FAIL |
|
|
|
Fire Alarm Review 1st
|