Permit Information
Permit NumberFIR06-01017
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 1314 W GROVE ST
Project NameMODERN HOTEL
Customer Number 
ePlanReview 
Description
To modify an existing manual/automatic fire alarm system. Plans include adding a NAC panel to provide visual alarm notification where required within the TI spaces and associated exit ways, to add a new DACT panel to transmit alarm signals offsite, to replace the existing pull stations with new devices and add additional pull stations as needed, to interconnect smoke alarms in newly created Suite rooms,

The associated building permit BLD06-02053 is to remodel an existing 20,208 square foot, non-sprinklered, hotel building (10,388 square foot 1st story and 9,820 square foot 2nd story). A 1,541 square foot area on the 1st story that was formerly a hotel lobby, an office, a caretaker's dwelling unit, and 2 guestrooms will be converted to a hotel lobby, an office, a bar, and a lounge. Within this area, work is to include 2 restrooms accessible to the disabled, beams, columns, concrete footings, millwork, and finishes. Within the remaining 41 guestrooms, work is to include remodeled bathrooms. A skylight will be installed above the 2nd story interior corridor and a new exterior stairway will be constructed. A total of five (5) suite guestroom will be provided. Each suite guestroom will be created by combining two regular guestrooms. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. DRH06-00266 **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/29/20075/29/20075/29/2007PPASS
DetailsForrest France
Required corrections verified for completion, fire alarm permit finaled.
INSP-Alarm Testing5/24/20075/25/20075/25/2007PCANC
DetailsForrest France
No time available to complete inspection today, to be rescheduled per conversation with contractor.
INSP-Final Inspection5/23/20075/24/20075/24/2007PFAIL
DetailsForrest France
See comments per inspection completed by M. Timmerman.
Inspection5/24/20075/24/20075/24/2007 FAIL
Fire Alarm Inspection
1.) Post Signs Leading to FACP
2.) Present Copy of Signals to Inspector
3.) Add Manual Pull Station to North Laundry Hall Exit
4.) Turn Down Audible Appliances by Laundry Area
5.) Single station smoke detectors not Interconnected where two smoke detectors are in large rooms
Telephone call  3/9/2007 DONE
telcon with Jeff at Electrical Engineering Co.; he indicated he is the designer for the system; discussed design requirements for a FACP replacement with upgraded capacity. Reviewed listed plan review comments, discussed IFC 102.1 and 907.10
Plan assigned to (Mike)12/26/2006 1/30/2007 PASS
1/30/2007 09:31:54 MWT - activity updated through activity FIRA22 from case FIR06-01017.
Alarm Plan Check1/29/2007 1/30/2007 PASS
Fire Alarm Review 2nd
PLANS/APPL TAKEN TO FRONT DESK  1/30/2007  
Ready for Issue
Inspection Record Card- Fire1/30/2007 1/30/2007 DONE
Telephone call  1/30/2007 DONE
telephone call to ken, permit ready to p/u fee $213
Permit Ready to Issue  1/30/2007 DONE
Issue and Print Permit  1/30/2007 DONE
Plan resubmittals received  1/23/2007  
Alarm Plan Check12/27/2006 1/11/2007 FAIL
review comments faxed to Allied, discussed with K. Webster.
Application received  12/26/2006  
Case Summary  12/26/2006