INSP-Final Inspection | 1/10/2008 | 1/10/2008 | 1/10/2008 | P | PASS |
Forrest France
|
|
|
Current as-builts recieved, fire sprinkler permit finaled.
|
INSP-Final Inspection | 12/14/2007 | 12/17/2007 | 12/17/2007 | A | FAIL |
Forrest France
|
|
|
As-built plans do not match field install, see branch line located in a wall adjacent to a closet missing coverage.
|
INSP-Final Inspection | 11/30/2007 | 12/3/2007 | 12/3/2007 | A | PART |
Forrest France
|
|
|
Final pending as-built plans for field modifications and floor plan changes.
|
INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 | P | PART |
Forrest France
|
|
|
Hydro test passed.
|
FIR-Aging Inspection | 6/19/2007 | 6/19/2007 | 6/19/2007 | | DONE |
Forrest France
|
|
|
Under construction, work in progress.
|
Permit Ready to Issue | | | 2/22/2007 | | DONE |
|
|
|
|
Telephone call | | | 2/22/2007 | | DONE |
|
|
|
call to lilly to p/u permit and fees $150
|
Issue and Print Permit | | | 2/22/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/22/2007 | | 1/22/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/8/2007 | | 1/19/2007 | | PASS |
|
|
|
Plan review by Bryan Johnson (cant release this permit until bldg permit is picked up and paid)
|
Application received | | | 1/8/2007 | | |
|
|
|
|
Pending Assignment by SAM | 1/8/2007 | | | | |
|
|
|
|