Permit NumberFIR07-00037
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1112 W MAIN ST Unit: 307
Project NameROYAL PLAZA
Customer Number 
ePlanReview 
Description
This TI in suite #307 includes dropping 15 residential heads into the new wall and ceiling layout of the dwelling unit. The work shall be performed in accordance with NFPA13R installation guidelines. This building is fully fire sprinklered for one-hour substitution. The fire sprinkler system work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD6-03315.
When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/16/20081/17/20081/17/2008APASS
DetailsForrest France
Verified as-built drawings, final pending light fixture obstruction as noted.
INSP-Final Inspection1/10/20081/11/20081/14/2008AFAIL
DetailsForrest France
As-built drawings do not match the floor plan, one head has been deleted, one head at the master bedroom is obstructed by a surface mounted light fixture.
INSP-Sprinkler Rough-in/Hydro1/10/20081/10/20081/10/2008PCANC
DetailsForrest France
Jonathon is contact Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Final Inspection12/14/200712/17/200712/17/2007AFAIL
DetailsForrest France
As-built plans are not accurate, one head is shown with no piping attatched, two heads are spaced incorrecty, missing head located in a closet next to the front door.
INSP-Final Inspection11/30/200712/3/200712/3/2007APART
DetailsForrest France
Install is satisfactory, final pending as-built plans for field mods. and floor plan changes.
INSP-Sprinkler Rough-in/Hydro10/25/200710/26/200710/29/2007PPART
DetailsForrest France
Hydro test passed.
FIR-Aging Inspection6/21/20076/21/20076/22/2007 DONE
DetailsForrest France
Work in progress.
Permit Ready to Issue  2/22/2007 DONE
Telephone call  2/22/2007 DONE
call to lilly to p/u permit and fees $150
Issue and Print Permit  2/22/2007 DONE
Inspection Record Card- Fire1/22/2007 1/22/2007 DONE
Sprinkler Plan Check1/9/2007 1/22/2007 PASS
Plan review by Bryan Johnson (cant release this permit until bld permit is picked up and paid)
Application received  1/9/2007  
Pending Assignment by SAM1/9/2007