Permit VOIDED | 9/24/2007 | 9/24/2007 | 9/24/2007 | | DONE |
|
|
|
void permit per Sam Rogers, this company no longer working on this project; replaced with fir07-00793
|
Telephone call | | | 8/22/2007 | | DONE |
|
|
|
Telcon with Randy, DeBest (###-####); they are to be replaced with another sprinkler contractor to redesign the system for 19' hi stge of Class II commdity (fruits and vegies in wooden and multi-ply CB crates, in single row racks without IR's, ord temp ceiling spk's; req's 0.34/2000sf density (avail density is 0.15). When new plans are submitted from a new contractor, this permit is to be voided and replaced with a new permit for the new contractor).
|
INSP-Sprinkler Rough-in/Hydro | 2/26/2007 | 2/27/2007 | 2/27/2007 | A | FAIL |
Troy Cobbley
|
|
|
Per the drawings and a subsequent phone conversation with Randy at DeBest, the sprinkler system in the coolers is designed for a .15 gpm density and is limited to a maximum storage height of 12'-0". The storage height as measured by me is at 19'-0". The system needs to be recalculated to the storage height being used or storage needs to be lowered pemanantly.
|
INSP-Final Inspection | 2/19/2007 | 2/20/2007 | 2/21/2007 | A | CANC |
Troy Cobbley
|
|
|
To be rescheduled since the fitter is sick today.
|
INSP-Final Inspection | 2/6/2007 | 2/7/2007 | 2/8/2007 | P | CANC |
Troy Cobbley
|
|
|
Per todd the canopies had to be reordered.
|
Sprinkler Plan Check | 1/11/2007 | | 1/11/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/11/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/11/2007 | | 1/11/2007 | | DONE |
|
|
|
|
Telephone call | | | 1/11/2007 | | DONE |
|
|
|
t/c w liz at DeBest Fire ###-#### - permit ready and fees given ($150.00)
|
Permit Ready to Issue | | | 1/11/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/11/2007 | | DONE |
|
|
|
|
Telephone call | | | 1/11/2007 | | DONE |
|
|
|
Spoke with Randy Bowron and discussed the criteria for which a fire sprinkler demo permit would be required. Informed Randy that a sprinkler demo permit for the costco cooler construction project would not be required.
|
Application received | | | 1/10/2007 | | |
|
|
|
|
Pending Assignment by SAM | 1/10/2007 | | | | |
|
|
|
|