Permit Information
Permit NumberFIR07-00050
StatusExpired
Name DEBEST FIRE PROTECTION
Site Address 101 N 10TH ST Unit: 204
Project NameGEM NOBLE BLDG
Customer Number 
ePlanReview 
Description
TI modification to shell sprinkler system installed under FIR06-00351.Add and relocate sprinklers on the second floor to accommodate a new wall and ceiling layout.
This permit is attached to BLD06-00709, FIR06—00351 / Shell & Core, UG permit FIR06-00226. . The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. Occupancy is not permitted until the Fire Department has certified by signature on the issued Permit by the Boise City Building Department, that the Shell & Core FIR06-00351) fire sprinkler system installation has been inspected and installed in compliance with an approved Fire Department inspection review. (IFC 105.3.3)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permit EXPIRED  3/15/2010 DONE
This work was completed by Idaho Fire Protection under permit FIR09-00056
Miscellaneous action  1/7/2010 DONE
DetailsTisha Gallop
Per Forrest reference Fir09-00056 for fire sprinkler inspections, do not do anything to this permit.
Case Summary  3/11/2008 DONE
INSP-Sprinkler Rough-in/Hydro3/23/20073/26/20073/26/2007APART
DetailsForrest France
Verified insulation install at ceiling pockets, OH rough-in is good for cover.
INSP-Sprinkler Rough-in/Hydro2/27/20072/28/20072/28/2007APART
DetailsForrest France
OH rough-in installation is acceptable, provide as-built plans for field modifications to pipe routing, need to verifiy non-sprinklered combustible cavities are completely filled with insulation for allowance of the exception per NFPA 13 prior to OH cover.
INSP-Sprinkler Rough-in/Hydro2/22/20072/23/20072/23/2007APART
DetailsForrest France
Inspection for OH cover at unit G5 only, shell and core plans marked for area inspected, noted pendent heads at some locations are in close proximity to electrical junction boxes and may present an obstruction depending on the type of light fixture installed, also noted field modifications which need to be shown on as-built plans.
INSP-Sprinkler Rough-in/Hydro2/21/20072/22/20072/22/2007PDEFR
DetailsForrest France
Inspection rescheduled per discussion with contractor.
Issue and Print Permit  1/19/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  1/18/2007 PASS
Inspection Record Card- Fire1/18/2007 1/18/2007 DONE
Permit Ready to Issue  1/18/2007 DONE
Telephone call  1/18/2007  
tlk to secretary for keith dilworht ###-#### that permit and fees are ready to be picked up
Application received  1/11/2007  
Case Summary  1/11/2007 DONE
Sprinkler Plan Check1/11/2007   PASS
Plan review by Bryan Johson
Pending Assignment by SAM1/11/2007