Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberFIR07-00085
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1301 N ORCHARD ST
Project NameMeasurement Inc.
Customer Number 
ePlanReview 
Description
This permit is to begin work on a fire alarm system for a new tenant that is to occupy the second level. Work includes elevator recall functions, shunt trip and shunt trip power monitoring. HVAC duct smoke detectors and continuation of the audible visual requirements for this building. Building permit # BLD07-00032 is to remodel an existing 13853 sq ft second floor office space per approved plans. Work to include, to remove 40 lf of nonbearing partitions and extend approximately 80 lf of partial height walls to eight feet high, this will still leave approximately 2 ft of clearnace to the existing ceiling system, installation of two new doors, and miscellaneous related interior finishes. This building is fully fire sprinkled ANY ALTERATIONS TO THE SPRINKLER SYSTEM WILL REQUIRE A SEPARATE PERMIT and shall be maintained per NFPA #13 as regulated by the fire department. The Fire alarm system is being installed under a separate permit. RMH
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/16/20072/16/20072/16/2007PPASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing2/15/20072/16/20072/16/2007APASS
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 2/15/2007 at 4:07:04 PM. Contact: ###-####.
Inspection2/16/20072/16/20072/16/2007 PASS
Fire Alarm System Inspection. Several problems all corrected durring the inspection time. 1.) Remove Door Hold Opens, 2.) Remove Non operative FA Devices, 3.) Relocate several Notification Appliances as shown on plans or Increase Candela. 4.) Correct HVAC shutdown, duct detector HVAC 9 5.) Elevator lobby smoke detectors to close to HVAC diffuser. 6.) Esccusion missing sprinkler head. 7.) Emergency lighting and exit sign not working 2nd Floor SW. The above items were corrected whial on site. Called Troy about life safety checks to make sure I didn't miss anything. All Pass
INSP-Alarm Testing2/14/20072/15/20072/15/2007ACANC
DetailsTroy Cobbley
To be canceled per the contractor due to hvac shutdown problems.
INSP-Alarm Testing2/13/20072/14/20072/14/2007PCANC
DetailsTroy Cobbley
Contractor was not ready the first time I showed up at the project. It was later decided to reschedule for when the elevator people could be there.
Issue and Print Permit  1/30/2007 DONE
Plan assigned to (Mike)1/23/2007 1/29/2007 PASS
1/29/2007 11:22:08 MWT - activity updated through activity FIRA22 from case FIR07-00085.
Alarm Plan Check1/26/2007 1/29/2007 PASS
Fire Alarm Review 1st
PLANS/APPL TAKEN TO FRONT DESK  1/29/2007  
Ready for Issue
Inspection Record Card- Fire1/29/2007 1/29/2007 DONE
Telephone call  1/29/2007  
spoke w/ john lopez, permit ready to p/u at $204.60
Permit Ready to Issue  1/29/2007 DONE
Case Summary  1/23/2007  
Plan resubmittals received  1/23/2007  
Application received  1/23/2007