INSP-Final Inspection | 2/16/2007 | 2/16/2007 | 2/16/2007 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Alarm Testing | 2/15/2007 | 2/16/2007 | 2/16/2007 | A | PASS |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 2/15/2007 at 4:07:04 PM. Contact: ###-####.
|
Inspection | 2/16/2007 | 2/16/2007 | 2/16/2007 | | PASS |
|
|
|
Fire Alarm System Inspection. Several problems all corrected durring the inspection time. 1.) Remove Door Hold Opens, 2.) Remove Non operative FA Devices, 3.) Relocate several Notification Appliances as shown on plans or Increase Candela. 4.) Correct HVAC shutdown, duct detector HVAC 9 5.) Elevator lobby smoke detectors to close to HVAC diffuser. 6.) Esccusion missing sprinkler head. 7.) Emergency lighting and exit sign not working 2nd Floor SW. The above items were corrected whial on site. Called Troy about life safety checks to make sure I didn't miss anything. All Pass
|
INSP-Alarm Testing | 2/14/2007 | 2/15/2007 | 2/15/2007 | A | CANC |
Troy Cobbley
|
|
|
To be canceled per the contractor due to hvac shutdown problems.
|
INSP-Alarm Testing | 2/13/2007 | 2/14/2007 | 2/14/2007 | P | CANC |
Troy Cobbley
|
|
|
Contractor was not ready the first time I showed up at the project. It was later decided to reschedule for when the elevator people could be there.
|
Issue and Print Permit | | | 1/30/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 1/23/2007 | | 1/29/2007 | | PASS |
|
|
|
1/29/2007 11:22:08 MWT - activity updated through activity FIRA22 from case FIR07-00085.
|
Alarm Plan Check | 1/26/2007 | | 1/29/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/29/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 1/29/2007 | | 1/29/2007 | | DONE |
|
|
|
|
Telephone call | | | 1/29/2007 | | |
|
|
|
spoke w/ john lopez, permit ready to p/u at $204.60
|
Permit Ready to Issue | | | 1/29/2007 | | DONE |
|
|
|
|
Case Summary | | | 1/23/2007 | | |
|
|
|
|
Plan resubmittals received | | | 1/23/2007 | | |
|
|
|
|
Application received | | | 1/23/2007 | | |
|
|
|
|