Case Summary | | | 2/12/2009 | | |
|
|
|
|
Miscellaneous action | | | 4/25/2008 | | DONE |
|
|
|
Plans sent to records for scanning.
|
INSP-Final Inspection | 3/28/2008 | 3/31/2008 | 3/31/2008 | A | PASS |
Forrest France
|
|
|
All corrections made per Forrest last inspection.The sound levels in the bedrooms furthest away from the current audible bells in the corridors PASSED per Dave Hanneman. KR
|
Agreement of Future work | 3/14/2006 | 6/15/2006 | 3/28/2008 | | DONE |
Tim Frost
|
|
|
Upgrade Agreement
|
Override - Parcel Holds | | | 3/28/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 3/28/2008 | | |
|
|
|
|
Case Summary | | | 3/11/2008 | | |
|
|
|
|
INSP-Final Inspection | 1/23/2008 | 1/23/2008 | 1/25/2008 | P | FAIL |
Forrest France
|
|
|
See 7 item correction notice and comments per inspection completed 1/24/08 for a list of items in need of revision.
|
Inspection | 1/24/2008 | 1/24/2008 | 1/24/2008 | A | PART |
Michael Timmerman
|
|
|
Idaho Building Fire Alarm Upgrade Inspection 1/24/2008: The inspection was conducted by Myself, Forrest France, and Tom Gainor the following items need to corrected. Before final.
1. OS&Y valves need to be adjusted so they report trouble when closed and switch is in the stem thread.
2. 6th Floor dry system tampers and fire alarm connections need to be correctly covered in a junction box and open connection installed properly in a J-Box with wire nuts not just tapped.
3. Light outside Satchels grill needs to be changed to "Red" with guard as submitted.
4. Install signage at new fire alarm light installed at Stachels grill indicating "Kitchen Hood Fire Alarm"
5. Post custom reset instructions in FACP for fire personnel
6. Install lockout and Identify breaker feeding FACP and Dialer power
7. Have NFPA 72 Forms ready when calling in for Last Inspection.
8. Keys to FACP must be located in Knox Box.
9. Add Audible Bell in West Corridor on levels 6, 5, 4, and 3
Note: Audible levels in furthest residential rooms with the outside and bedroom doors closed did not move the Inspection db Meter which lowest setting is 60db off of Zero. The bell could be heard but we suspect the audible level would not alert someone sleeping or would not be heard with the TV playing. The db readings shown on the submitted plans must not have been conducted inside the rooms with doors closed. or any ambient background noise.
|
Override - Parcel Holds | | | 1/23/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 1/23/2008 | | |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/4/2008 | | DONE |
|
|
|
|
(F) Reprint permit | | | 1/4/2008 | | DONE |
|
|
|
|
Alarm Plan Check | 12/31/2007 | | 12/31/2007 | | PASS |
Michael Timmerman
|
|
|
Fire Alarm Review 3rd - Subject to field Inspection and review comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/31/2007 | | DONE |
|
|
|
Ready for Re-Issue
|
Override - Parcel Holds | | | 12/31/2007 | | |
|
|
|
|
Override - Parcel Holds | | | 12/31/2007 | | |
|
|
|
|
Inspection Record Card- Fire | 12/31/2007 | | 12/31/2007 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/31/2007 | | DONE |
|
|
|
left vm for ken howell at ###-#### x27 - permit ready and fees given
|
Override - Parcel Holds | | | 12/31/2007 | | |
|
|
|
|
Override - Parcel Holds | | | 12/31/2007 | | |
|
|
|
|
Permit Ready to Issue | | | 12/31/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/28/2007 | | |
|
|
|
plan modification; recieved one application, three folders of submittal info and sets of plans
|
Plan assigned to (Mike) | 12/28/2007 | | 12/28/2007 | | |
|
|
|
Resubmittal Indicating Panel Added
|
Inspection | 9/20/2007 | 9/20/2007 | 9/20/2007 | | |
|
|
|
Mike Timmerman - Tom Gainor , Both went to the Idaho Building to check repair work on the fire alarm system due to problems with the alarm system upgrade and repair work installation. Many problems have been occurring and the offsite reporting has not been working. The building representative called Tom and said that the fire alarm panel had been corrected again and wanted to remove the fire watch. Tom and I went to witness that the fire alarm panel was working again and get a status on the upgrade project. No plans were on site, however, the alarm contractor said that they were very close to finishing. We conducted a simple manual pull station test and the "Test Failed". The alarm bells went off but the supervising station did not get a correct alarm signal and no reporting of an alarm was made to Ada county dispatch .
|
FIR-Aging Inspection | 8/22/2007 | 8/22/2007 | 8/23/2007 | | DEFR |
Forrest France
|
|
|
Work in progress.
|
Override - Parcel Holds | | | 4/10/2007 | | |
|
|
|
|
Override - Parcel Holds | | | 4/10/2007 | | |
|
|
|
|
Case Summary | | | 3/5/2007 | | |
|
|
|
|
Override - Parcel Holds | | | 3/2/2007 | | |
|
|
|
|
Override - Parcel Holds | | | 3/2/2007 | | |
|
|
|
|
Issue and Print Permit | | | 3/2/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/1/2007 | | |
|
|
|
Ready for Issue
|
Override - Parcel Holds | | | 3/1/2007 | | |
|
|
|
|
Override - Parcel Holds | | | 3/1/2007 | | |
|
|
|
|
Inspection Record Card- Fire | 3/1/2007 | | 3/1/2007 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 3/1/2007 | | |
|
|
|
|
Override - Parcel Holds | | | 3/1/2007 | | |
|
|
|
|
Permit Ready to Issue | | | 3/1/2007 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 3/1/2007 | | |
|
|
|
|
Telephone call | | | 3/1/2007 | | DONE |
|
|
|
call to ken howell, permit ready to p/u.
|
Alarm Plan Check | 2/27/2007 | | 2/28/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
Plan resubmittals received | | | 2/26/2007 | | |
|
|
|
|
Plan resubmittals received | | | 2/21/2007 | | |
|
|
|
|
Telephone call | | | 2/9/2007 | | DONE |
|
|
|
call to ken howell, voice mail msg left, to p/u plans and resubmit
|
Miscellaneous action | | | 2/9/2007 | | |
|
|
|
Faxed Copy of Review to Parklane Management (Ken Howell) and ECI Mary Froemky
|
Alarm Plan Check | 2/6/2007 | | 2/7/2007 | | FAIL |
|
|
|
Fire Alarm Review
|
Application received | | | 1/29/2007 | | |
|
|
|
|
Case Summary | | | 1/29/2007 | | DONE |
|
|
|
|