INSP-Final Inspection | 7/24/2007 | 7/26/2007 | 7/26/2007 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 7/24/2007 | 7/25/2007 | 7/25/2007 | A | FAIL |
Troy Cobbley
|
|
|
Need the shell core permit finaled first. This permit will be ready to final when that is done.
|
INSP-Sprinkler Rough-in/Hydro | 7/20/2007 | 7/20/2007 | 7/20/2007 | P | PASS |
Troy Cobbley
|
|
|
Hydro Test of the second floor passed.
|
INSP-Final Inspection | 7/18/2007 | 7/19/2007 | 7/19/2007 | P | CANC |
Troy Cobbley
|
|
|
Was to be called in when the fire alarm was ready. It wasn't
|
INSP-Sprinkler Rough-in | 7/13/2007 | 7/16/2007 | 7/16/2007 | A | PASS |
Troy Cobbley
|
|
|
OH Cover Inspection for the stairwells and first floor corridor.
|
INSP-Sprinkler Rough-in | 7/3/2007 | 7/5/2007 | 7/5/2007 | A | PASS |
Troy Cobbley
|
|
|
The second floor tenant improvement sprinkler piping is ok to cover. Four hangers need to be added in the Conference room to the west of the elevators. The room in the northwest corner of the building is experiencing changes and has no ceiling yet.
|
INSP-Sprinkler Rough-in | 6/26/2007 | 6/27/2007 | 6/27/2007 | A | PASS |
Troy Cobbley
|
|
|
The two pendants in the south side soffit of the second floor elevator lobby are ok to cover
|
INSP-Sprinkler Rough-in | 6/5/2007 | 6/6/2007 | 6/7/2007 | P | FAIL |
Troy Cobbley
|
|
|
Rough Inspection for the 5th floor installation was ok but the plans need to be resubmitted due to riser nipples being added to the gridded system. I also inspected both standpipes except for the roof manifold and the 5th floor riser.
|
INSP-Supply line flush | 6/5/2007 | 6/7/2007 | 6/7/2007 | A | PASS |
Troy Cobbley
|
|
|
UG flush passed
|
Case Summary | | | 6/6/2007 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 5/29/2007 | 5/29/2007 | 5/29/2007 | P | PASS |
Troy Cobbley
|
|
|
The sprinkler piping located above the hardlid/closet areas are ok to cover
|
INSP-Sprinkler Rough-in | 5/24/2007 | 5/25/2007 | 5/25/2007 | P | NR |
Forrest France
|
|
|
Work not yet completed for inspection.
|
FIR-Aging Inspection | 5/11/2007 | 5/11/2007 | 5/11/2007 | | NR |
Troy Cobbley
|
|
|
Work is in progress
|
Issue and Print Permit | | | 2/9/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/8/2007 | | |
|
|
|
|
Inspection Record Card- Fire | 2/8/2007 | | 2/8/2007 | | DONE |
|
|
|
|
Telephone call | | | 2/8/2007 | | DONE |
|
|
|
lft ms with secretary for randy bowman ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 2/8/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/2/2007 | | 2/5/2007 | | PASS |
|
|
|
Plan review by Bryan Johnson
|
Application received | | | 2/2/2007 | | |
|
|
|
|
Pending Assignment by SAM | 2/2/2007 | | | | |
|
|
|
|