INSP-Final Inspection | 2/21/2007 | 2/22/2007 | 2/22/2007 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/19/2007 | 2/20/2007 | 2/21/2007 | A | FAIL |
Troy Cobbley
|
|
|
Booth suppression system activated when the test link was cut. The air supply for painting shut off as well. The booth does not have the 3' clearance as required but seems to meet the exception for being against a non combustible wall. The wall is cinderblock which supports a sheetrock ceiling. The item that is a problem is the heater for the curing/baking process is direct fire which is not allowed per code. Also the distance from property lines and openings needs verified as well as the height of the exhaust discharge piping. Matt was going to have his booth supplier contact sam rogers about their booth and its operation. Also I had matt program in the required 3 minute delay before the heater comes on per code and per matt the unit has a high limit switch set at 200 degrees. The fire extinguisher is also ok.
|
INSP-Final Inspection | 2/15/2007 | 2/16/2007 | 2/16/2007 | P | CANC |
Troy Cobbley
|
|
|
Per contractor piping needs to be rerouted around electrical cabinet. No inspection was performed.
|
Inspection Record Card- Fire | 2/15/2007 | | 2/15/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/15/2007 | | DONE |
|
|
|
|
Telephone call | | | 2/15/2007 | | DONE |
|
|
|
call to don, permit ready to p/u and fees $150
|
Issue and Print Permit | | | 2/15/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/14/2007 | | |
|
|
|
|
Sprinkler Plan Check | 2/14/2007 | | 2/14/2007 | | PASS |
|
|
|
Passed with notes on plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/14/2007 | | DONE |
|
|
|
|
Telephone call | | | 2/13/2007 | | DONE |
|
|
|
call to Don Kartchner, told him plans failed need to be resubmitted. Kartchner stated that he would like me to fax plans to him. Plans faxed.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/12/2007 | | DONE |
|
|
|
|
Application received | | | 2/8/2007 | | |
|
|
|
|
Case Summary | | | 2/8/2007 | | |
|
|
|
|
Sprinkler Plan Check | 2/12/2007 | | | | FAIL |
|
|
|
Fax transmission failed to contranctor. Resubmittal items are attached to original application. Contractor will have to come pick up.
|
Pending Assignment by SAM | 2/8/2007 | | | | |
|
|
|
|