INSP-Final Inspection | 12/6/2007 | 12/6/2007 | 12/6/2007 | P | PASS |
Forrest France
|
|
|
Shell and core fire alarm permit passed final inspection, as-built documentation to be delivered as discussed.
|
INSP-Final Inspection | 12/5/2007 | 12/5/2007 | 12/5/2007 | A | FAIL |
Forrest France
|
|
|
Need correction notice items one and two completed prior to final acceptance, also noted SD covers at three locations.
|
INSP-Final Inspection | 12/4/2007 | 12/4/2007 | 12/4/2007 | P | FAIL |
Forrest France
|
|
|
See correction notice left on site for a list of items needed for permit final.
|
INSP-Final Inspection | 11/29/2007 | 11/29/2007 | 11/29/2007 | P | PART |
Forrest France
|
|
|
Fire alarm passed. Cannot final, pending core and shell final.KR
|
INSP-Final Inspection | 11/28/2007 | 11/28/2007 | 11/28/2007 | P | DEFR |
Forrest France
|
|
|
See inspection comments per M. Timmerman.
|
Inspection | 11/28/2007 | | 11/28/2007 | P | FAIL |
Michael Timmerman
|
|
|
Shell & Core Area Correction Inspection, Tested Dry System Fire Alarm Devices, Basement Electrical Room Tamper Switches - OK: "Fail" Roof Top Unit AHU Shutdown Not Working, Stairway Pressurization Fans Do Not Shutdown on Reset; "Found Relays to Small for Motor Load Contacts Sticking Together" Larger Relays are Needed for Stairway Pressurization Fans. Elevator Fire Phones Not Complete, Knox Box Not Installed. Area of Refuge Placards Installed, Need to Determine if Stairway is Area of Refuge Why are These Signs Up.
|
INSP-Final Inspection | 11/27/2007 | 11/27/2007 | 11/27/2007 | P | CANC |
Forrest France
|
|
|
Overbooked.
|
INSP-Alarm Testing | 11/23/2007 | 11/23/2007 | 11/23/2007 | P | PART |
Forrest France
|
|
|
Inspection activity completed 11/21 including shell and core alarm work for the 4th thru 6th and penthouse testing, also tested sprinkler monitoring for the floor control valves, noted some items in need of correction including programming for the DH release at the trash chute doors, as-built address changes, and field mods.
|
INSP-Alarm Testing | 11/19/2007 | 11/20/2007 | 11/20/2007 | A | PART |
Forrest France
|
|
|
Begin fire alarm testing today including all related elevator control devices, FACP, batteries, phone lines, smoke at panel,FJ and initiation and detection devices for the 1st thru 3rd floors not including sprinkler monitoring tested today. Noted some device address changes, three deleted ID detectors, one pull station at the NW exit is still too high, need to provide a clean set of as-builts for field modifications and a current map at the panel.
|
Inspection Record Card- Fire | 3/5/2007 | | 3/5/2007 | | DONE |
|
|
|
|
Alarm Plan Check | 2/26/2007 | | 2/26/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/26/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 2/26/2007 | | 2/26/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/26/2007 | | DONE |
|
|
|
|
Telephone call | | | 2/26/2007 | | |
|
|
|
CALL TO
|
Telephone call | | | 2/26/2007 | | |
|
|
|
CALL TO ROB AHTHEN, PERMIT READY TO P/U. NO FEE
|
CHANGE STATUS TO (ISS) | | | 2/26/2007 | | |
|
|
|
new commercial -no fee due
|
Plan assigned to (Mike) | 2/12/2007 | | 2/26/2007 | | PASS |
|
|
|
2/26/2007 11:49:47 MWT - activity updated through activity FIRA22 from case FIR07-00129.
|
Plan resubmittals received | | | 2/16/2007 | | |
|
|
|
|
Alarm Plan Check | 2/14/2007 | | 2/15/2007 | | FAIL |
|
|
|
Fire Alarm Review 1st
|
Miscellaneous action | | | 2/15/2007 | | |
|
|
|
Fax review comments to fire alarm vendor, Rob Ahten Protex ###-####
|
Miscellaneous action | | | 2/15/2007 | | |
|
|
|
Take Plans to Permit dest for Resubmittal
|
Telephone call | | | 2/15/2007 | | DONE |
|
|
|
CALL TO ROB AHTEN TO P/U PLANS AND RESUBMIT
|
Application received | | | 2/12/2007 | | |
|
|
|
|
Case Summary | | | 2/12/2007 | | DONE |
|
|
|
|