INSP-Final Inspection | 11/8/2007 | 11/9/2007 | 11/9/2007 | A | PASS |
Forrest France
|
|
|
Picked up copy of state elevator permit for final and NFPA record of completion.
|
INSP-Final Inspection | 6/13/2007 | 6/14/2007 | 6/15/2007 | A | PART |
Forrest France
|
|
|
FA permit okay for final pending verification of satisfactory state elevator inspection.
|
INSP-Alarm Testing | 4/11/2007 | 4/12/2007 | 4/12/2007 | P | PART |
Forrest France
|
|
|
Noted c/n items from the previous inspection have been completed, one additional SD at the hoistway to be installed when work on the second car is complete, final pending.
|
INSP-Alarm Testing | 4/6/2007 | 4/9/2007 | 4/10/2007 | P | FAIL |
Forrest France
|
|
|
Notification audibility in the mech equip. penthouse is below minimum dB allowed, provide an additional SD at the top of the hoistway due to beam obstruction, the firemans hat in the car must flash intermittently upon equipment room or hoistway FA device activation.
|
Plan assigned to (Mike) | 2/16/2007 | | 2/27/2007 | | PASS |
|
|
|
2/27/2007 08:30:23 MWT - activity updated through activity FIRA22 from case FIR07-00156.
|
Alarm Plan Check | 2/26/2007 | | 2/27/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/27/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 2/27/2007 | | 2/27/2007 | | DONE |
|
|
|
|
Telephone call | | | 2/27/2007 | | DONE |
|
|
|
t/c w jim shilton at honeywell inc. ###-#### - permit ready and fees given ($204.60)
|
Permit Ready to Issue | | | 2/27/2007 | | |
|
|
|
|
Issue and Print Permit | | | 2/27/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/27/2007 | | DONE |
|
|
|
|
Case Summary | | | 2/16/2007 | | |
|
|
|
|
Application received | | | 2/16/2007 | | |
|
|
|
|