Permit NumberFIR07-00156
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project NameSt Lukes Central Elevator
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install new fire alarm devices as required for an owner initiated elevator upgrade in the central building. The existing elevator controllers which do not have the capability of elevator recall are to be replaced with elevator controllers that do. Smoke Guard doors are to be installed in front of each elevator on all levels. Smoke detectors will be installed in each elevator lobby and will be used for elevator recall and smoke guard door release. Fire alarm devices will be added to the penthouse elevator equipment room for elevator power shutdown (shunt trip) and fire hat warning. A manual pull station and notification appliance will also be installed in the elevator equipment room. A smoke and two heat detectors are shown to be installed at the top of the elevator shaft.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/8/200711/9/200711/9/2007APASS
DetailsForrest France
Picked up copy of state elevator permit for final and NFPA record of completion.
INSP-Final Inspection6/13/20076/14/20076/15/2007APART
DetailsForrest France
FA permit okay for final pending verification of satisfactory state elevator inspection.
INSP-Alarm Testing4/11/20074/12/20074/12/2007PPART
DetailsForrest France
Noted c/n items from the previous inspection have been completed, one additional SD at the hoistway to be installed when work on the second car is complete, final pending.
INSP-Alarm Testing4/6/20074/9/20074/10/2007PFAIL
DetailsForrest France
Notification audibility in the mech equip. penthouse is below minimum dB allowed, provide an additional SD at the top of the hoistway due to beam obstruction, the firemans hat in the car must flash intermittently upon equipment room or hoistway FA device activation.
Plan assigned to (Mike)2/16/2007 2/27/2007 PASS
2/27/2007 08:30:23 MWT - activity updated through activity FIRA22 from case FIR07-00156.
Alarm Plan Check2/26/2007 2/27/2007 PASS
Fire Alarm Review 1st
PLANS/APPL TAKEN TO FRONT DESK  2/27/2007  
Ready for Issue
Inspection Record Card- Fire2/27/2007 2/27/2007 DONE
Telephone call  2/27/2007 DONE
t/c w jim shilton at honeywell inc. ###-#### - permit ready and fees given ($204.60)
Permit Ready to Issue  2/27/2007  
Issue and Print Permit  2/27/2007 DONE
Issue and Print Permit  2/27/2007 DONE
Case Summary  2/16/2007  
Application received  2/16/2007