INSP-Final Inspection | 5/16/2007 | 5/17/2007 | 5/17/2007 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled and performed by Mike Timmerman
|
Inspection | 5/17/2007 | 5/17/2007 | 5/17/2007 | | PASS |
|
|
|
Fire Alarm System Inspection: Reinspection of entire system with Brian at Simplex. Tested notification, initiating devices sprinkler system monitoring, water flow, duct smoke detectors and Kitchen hood alarm Pass by a hair.
|
INSP-Final Inspection | 5/10/2007 | 5/11/2007 | 5/11/2007 | P | FAIL |
Forrest France
|
|
|
See inspection notes per M. Timmerman.
|
Inspection | 5/11/2007 | 5/11/2007 | 5/11/2007 | | FAIL |
|
|
|
Fire alarm inspection request - Fail
1.) Both north restroom notification appliances hanging by the fire alarm wires.
2.) Notification appliance in fire alarm room needs cd to be increased not located as on plans.
3.) Added notification appliance behind hood needs to be increased to a minimum of 30cd.
4.) Notification appliance covered with painters tape & paper
5.) Standard duct detectors mounted on HVAC units outside in the elements not NEMA rated for outdoor use, temperature range is 32degF - 100def F
6.) A full inspection needs to be done again project not ready.
|
Plan assigned to (Mike) | 2/20/2007 | | 2/27/2007 | | PASS |
|
|
|
2/27/2007 12:24:31 MWT - activity updated through activity FIRA22 from case FIR07-00159.
|
Alarm Plan Check | 2/27/2007 | | 2/27/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/27/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 2/27/2007 | | 2/27/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/27/2007 | | 2/27/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/27/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/27/2007 | | DONE |
|
|
|
|
Application received | | | 2/20/2007 | | |
|
|
|
|