Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR07-00159
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 610 W IDAHO ST
Project NameOLD SPAGHETTI FACTORY
Customer Number 
ePlanReview 
Description
This permit is to install a new required manual fire alarm system with sprinkler, HVAC and kitchen hood suppression monitoring. Audible visual notification appliances are to be installed as required by code and offsite supervising station reporting. Building permit BLD06-02665 is to construct a restaurant within a 10,584 square foot, 1 story building. Work is to include interior nonbearing walls, three restrooms accessible to the disabled, a unisex restroom accessible to the disabled, suspended acoustical ceilings, suspended wood ceilings, suspended gypsum board ceilings, interior doors, interior windows, millwork, and finishes. The building shell work (seismic upgrade, alterations to the roof structure, new wall openings, a new concrete slab on grade, fixed awnings, and new exterior windows and doors) was done under permit BLD06-02785. Interior non-structural demolition was done under permit BLD06-03204. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. DRH06-00273 **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/16/20075/17/20075/17/2007APASS
DetailsTroy Cobbley
Permit finaled and performed by Mike Timmerman
Inspection5/17/20075/17/20075/17/2007 PASS
Fire Alarm System Inspection: Reinspection of entire system with Brian at Simplex. Tested notification, initiating devices sprinkler system monitoring, water flow, duct smoke detectors and Kitchen hood alarm Pass by a hair.
INSP-Final Inspection5/10/20075/11/20075/11/2007PFAIL
DetailsForrest France
See inspection notes per M. Timmerman.
Inspection5/11/20075/11/20075/11/2007 FAIL
Fire alarm inspection request - Fail
1.) Both north restroom notification appliances hanging by the fire alarm wires.
2.) Notification appliance in fire alarm room needs cd to be increased not located as on plans.
3.) Added notification appliance behind hood needs to be increased to a minimum of 30cd.
4.) Notification appliance covered with painters tape & paper
5.) Standard duct detectors mounted on HVAC units outside in the elements not NEMA rated for outdoor use, temperature range is 32degF - 100def F
6.) A full inspection needs to be done again project not ready.
Plan assigned to (Mike)2/20/2007 2/27/2007 PASS
2/27/2007 12:24:31 MWT - activity updated through activity FIRA22 from case FIR07-00159.
Alarm Plan Check2/27/2007 2/27/2007 PASS
Fire Alarm Review 1st
PLANS/APPL TAKEN TO FRONT DESK  2/27/2007  
Ready for Issue
Inspection Record Card- Fire2/27/2007 2/27/2007 DONE
Inspection Record Card- Fire2/27/2007 2/27/2007 DONE
Permit Ready to Issue  2/27/2007 DONE
Issue and Print Permit  2/27/2007 DONE
Application received  2/20/2007