Permit Information
Permit NumberFIR07-00166
StatusFinaled
Name ROMAR ELECTRIC
Site Address 1111 W JEFFERSON ST
Project NameBoise Bldg 4th & 5th Floors
Customer Number 
ePlanReview 
Description
This permit is to install audible visual notification appliances in several Non-Occupied areas of the 4th and 5th floors in the Boise Building. No building permit is associated with this work. The fire alarm work to be completed is part of the building fire alarm upgrade agreement. The original approved upgrade agreement permit number is FIR06-00595.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/4/2008 DONE
Plans taken to records to scan
INSP-Final Inspection4/28/20084/28/20084/29/2008PPASS
DetailsForrest France
Fire alarm permit work scope is approved for final-some locations eclipsed by subsequent tenant fire alarm modifications inspected under respective permits for the 5th and 4th floors.
INSP-Alarm Testing8/23/20078/24/20078/24/2007APART
DetailsForrest France
Re-inspection for the fire alarm work associated with the 4th floor remodel BLD07-01120 passed, remainder of alarm permit scope of work not yet completed.
INSP-Alarm Testing8/22/20078/23/20078/23/2007AFAIL
DetailsForrest France
Overspaced SD at the cafeteria, strobe coverage is lacking at one area in the kitchen, audibility is too low for the kitchen service/prep area, remainder of the 4th floor west half as tested is acceptable.
INSP-Alarm Testing4/12/20074/13/20074/13/2007APART
DetailsForrest France
Testing completed for the south half of the 4th floor including one added device, pull stations at the exit stairs, SD at the service elevator, SD for stairwell fans, and retest of the telephone and electrical room detection.
Issue permit  3/8/2007 DONE
Inspection Record Card- Fire3/7/2007 3/7/2007 DONE
Permit Ready to Issue  3/7/2007 DONE
Telephone call  3/7/2007 DONE
call to wes smith, left msg on v/m, permit ready to p/u
Alarm Plan Check3/6/2007 3/6/2007 PASS
Fire Alarm Review 2nd
PLANS/APPL TAKEN TO FRONT DESK  3/6/2007  
Ready for Issue
Plan assigned to (Mike)2/22/2007 3/6/2007 PASS
3/6/2007 18:55:15 MWT - activity updated through activity FIRA22 from case FIR07-00166.
Alarm Plan Check2/22/2007 2/23/2007 FAIL
DetailsMichael Timmerman
Fire Alarm Review 1st
Telephone call  2/23/2007  
Left Voicemail Scott Schainer ###-#### for resubmittal required
Miscellaneous action  2/23/2007  
Fax copy of review to Applicant, Romar Electric Wes Smith
Telephone call  2/23/2007  
Called Sandy ###-#### for Resubmittal
Telephone call  2/23/2007  
re-submittal required per mike t.
Application received  2/22/2007  
Inspection3/27/20073/27/2007  FAIL
After hours Inspection Boise Cascade Building. ( Fail)

1.) The installing contractor is using a non- approved set of floor plans for installation of fire alarm equipment on the 4th floor. The approved set of plans was found in the general contractor's office, and after review the installation was significantly different than what was on the approved set of plans.

2.) Began by testing a smoke detector outside of the Northeast stairwell, found that an alarm verification feature is programmed into the automatic fire alarm detection devices. The main FACP descriptor associated with the smoke detector had only confusing identification numbers with no association to the floor or area of the detector location.

3.) Tested another smoke detector outside of freight elevator, alarm verification was enabled on this detector also. Finally after the detector went into alarm the smoke guard doors released and another confusing descriptor displayed at the main FACP. This time the descriptor said that the alarm was at the plaza level elevator smoke detector.

4.) It was decided that a meeting needs to be set up to discuss the procedure for installation, testing and correcting problems found during inspections. Also determine why installing workers are not working from approved plans.