Permit Information
Permit NumberFIR07-00190
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project Name 
Customer NumberC10213
ePlanReview 
Description
Fire Alarm System: C10213 Install TEL PIR Hood - The installation of a Tel PIR Hood to B15-SA1524 will require a modification of the existing fire alarm system in the building. A clean room wall be relocated to accommodate the tool, and horn/strobe coverage will be adjusted per the new architectural layout and brought to current code compliance. Existing heat dectectors associated with the building preaction system will be relocated. An integral CO2 fire suppression system in the new hood will be monitored for alarm and trouble.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  6/21/2007 DONE
INSP-Alarm Testing5/17/20075/18/20075/18/2007APASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing5/9/20075/11/20075/11/2007AFAIL
DetailsForrest France
Missing audible notification at the agent cabinets.
Sprinkler Plan Check3/9/2007 3/9/2007 PASS
Plan modification "REV O"; revision adds a second hood internal CO2 system to be monitored for discharge "alarm" and circuit "trouble".
Issue and Print Permit  3/7/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  3/6/2007 DONE
Alarm Plan Check3/1/2007 3/1/2007 DONE
on site review; approved subject to plan annotations.
Application received  2/28/2007 DONE
This permit was created on the web by Paul Marcolina