Miscellaneous action | | | 4/25/2008 | | DONE |
|
|
|
Plans sent to records for scanning.
|
INSP-Final Inspection | 2/21/2008 | 2/22/2008 | 2/22/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm inspection complete. KR
|
INSP-Final Inspection | 2/15/2008 | 2/20/2008 | 2/20/2008 | A | FAIL |
Troy Cobbley
|
|
|
System was completely tested. found that they were not ready to test duct detectors,Also found that sprinkler bell rings on general building alarm, not water flow. Mangates on outside of building did not release during fire alarm, gates are access to public way. KR
|
FIR-Aging Inspection | 8/20/2007 | 8/20/2007 | 8/24/2007 | | NR |
Troy Cobbley
|
|
|
work is in progress
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/8/2007 | | |
|
|
|
Ready for Issue
|
Permit Ready to Issue | | | 5/8/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/8/2007 | | 5/8/2007 | | DONE |
|
|
|
|
Telephone call | | | 5/8/2007 | | DONE |
|
|
|
call to mike fease, permit ready to p/u and fee is $826.20
|
Issue and Print Permit | | | 5/8/2007 | | DONE |
|
|
|
|
Alarm Plan Check | 5/3/2007 | | 5/7/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
Plan resubmittals received | | | 4/30/2007 | | |
|
|
|
Received fire alarm application, info on devices, miscellaneous, battery calculations, flow calculations, voltage calculations, info on caterpillar power generation system, equipment data sheets, and two copies of full set of plans; taken to fire review
|
Telephone call | | | 3/14/2007 | | DONE |
|
|
|
t/c w mike fease - ###-#### - re-submittal required - he will be down today to pick it up
|
Telephone call | | | 3/14/2007 | | |
|
|
|
gave plans to customer needed resubmittal requirements
|
Alarm Plan Check | 3/13/2007 | | 3/13/2007 | | FAIL |
|
|
|
Fire Alarm Review 1st
|
Miscellaneous action | | | 3/13/2007 | | |
|
|
|
Fax copy of fire alarm review to applicant, Mike Fease. ###-####
|
Plan assigned to (Mike) | 3/1/2007 | | 3/8/2007 | | PASS |
|
|
|
3/8/2007 09:18:57 CMC - activity updated through activity FIRA22 from case FIR06-00988.
|
Case Summary | | | 3/1/2007 | | |
|
|
|
|
Application received | | | 3/1/2007 | | |
|
|
|
|
INSP-Final Inspection | 2/20/2008 | 2/21/2008 | | A | |
Kenneth R Roule
|
|
|
randy barnett Phone #: ###-####
|