Permit Information
Permit NumberFIR07-00199
StatusFinaled
Name GENERAL FIRE INC
Site Address 12877 W MCMILLAN RD
Project NameVERIZON WIRELESS
Customer Number 
ePlanReview 
Description
This permit is to install a new addressable fire detection system using the Notifier NFS-640. The new fire alarm panel will be used as the release panel for a double interlock pre-action sprinkler system and the FM 200 clean agent suppression systems. The manual pull stations, flow switches, supervisory switches will be connected to the Notifier NFS-640 panel. New Fike SHP will be installed for the new protection spaces and the two existing SHP panels will be relocated to accommodate the removal of existing walls. Building Permit BLD06-00749 is to construct a 6,673 sq. ft. Type IIB one story addition to the existing Verizon switch gear office building and to remodel the interior of the existing building. Other work includes all site improvements, paving and landscaping per approved plans and attachments, CUP05-00165. This building is partially fire sprinkled.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/25/2008 DONE
Plans sent to records for scanning.
INSP-Final Inspection2/21/20082/22/20082/22/2008APASS
DetailsForrest France
Fire alarm inspection complete. KR
INSP-Final Inspection2/15/20082/20/20082/20/2008AFAIL
DetailsTroy Cobbley
System was completely tested. found that they were not ready to test duct detectors,Also found that sprinkler bell rings on general building alarm, not water flow. Mangates on outside of building did not release during fire alarm, gates are access to public way. KR
FIR-Aging Inspection8/20/20078/20/20078/24/2007 NR
DetailsTroy Cobbley
work is in progress
PLANS/APPL TAKEN TO FRONT DESK  5/8/2007  
Ready for Issue
Permit Ready to Issue  5/8/2007 DONE
Inspection Record Card- Fire5/8/2007 5/8/2007 DONE
Telephone call  5/8/2007 DONE
call to mike fease, permit ready to p/u and fee is $826.20
Issue and Print Permit  5/8/2007 DONE
Alarm Plan Check5/3/2007 5/7/2007 PASS
Fire Alarm Review 2nd
Plan resubmittals received  4/30/2007  
Received fire alarm application, info on devices, miscellaneous, battery calculations, flow calculations, voltage calculations, info on caterpillar power generation system, equipment data sheets, and two copies of full set of plans; taken to fire review
Telephone call  3/14/2007 DONE
t/c w mike fease - ###-#### - re-submittal required - he will be down today to pick it up
Telephone call  3/14/2007  
gave plans to customer needed resubmittal requirements
Alarm Plan Check3/13/2007 3/13/2007 FAIL
Fire Alarm Review 1st
Miscellaneous action  3/13/2007  
Fax copy of fire alarm review to applicant, Mike Fease. ###-####
Plan assigned to (Mike)3/1/2007 3/8/2007 PASS
3/8/2007 09:18:57 CMC - activity updated through activity FIRA22 from case FIR06-00988.
Case Summary  3/1/2007  
Application received  3/1/2007  
INSP-Final Inspection2/20/20082/21/2008 A 
DetailsKenneth R Roule
randy barnett Phone #: ###-####