Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR07-00209
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 777 W BROAD ST
Project NameBODO BLDG #8 - SPR
Customer Number 
ePlanReview 
Description
Add 7 SSU & relocate 1 SSP as required for new light haz. TI. occupancy per NFPA 13 2002.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/4/20075/7/20075/7/2007APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection3/21/20073/26/20073/26/2007PPART
DetailsForrest France
Corrections from previous inspection have been finished, need to install drop ceiling and escutcheons prior to final.
INSP-Sprinkler Rough-in/Hydro3/15/20073/16/20073/16/2007AFAIL
DetailsForrest France
Static pressures above 100 psi. require hangers within 1' of the end on armovers supplying pendent sprinklers at the ATM lobby.
Permit Ready to Issue  3/12/2007 DONE
Inspection Record Card- Fire3/12/2007 3/12/2007 DONE
Telephone call  3/12/2007 DONE
call to gereald ebeling, permit ready to p/u, $150
Issue and Print Permit  3/12/2007  
Sprinkler Plan Check3/9/2007 3/9/2007 PASS
PLANS/APPL TAKEN TO FRONT DESK  3/9/2007 DONE
Application received  3/8/2007