INSP-Final Inspection | 5/9/2007 | 5/10/2007 | 5/10/2007 | A | PASS |
Forrest France
|
|
|
Final FS permit inspection passed, corrections complete.
|
INSP-Final Inspection | 5/4/2007 | 5/7/2007 | 5/7/2007 | A | PART |
Forrest France
|
|
|
Pending ceiling tile, lockout at the air comp. switch as discussed.
|
Inspection | 5/4/2007 | 5/4/2007 | 5/4/2007 | | PART |
|
|
|
Tested pre-action sprinkler system operation with the fire alarm contractor. The programming was inaccurate for a double interlock system it required a low air and two smoke detectors to be in alarm. I inspected other items whial the corrected the alarm system programming on the preaction system. Retested pre-action operation and it worked fine.
|
INSP-Sprinkler Rough-in/Hydro | 5/2/2007 | 5/3/2007 | 5/3/2007 | P | PART |
Forrest France
|
|
|
Air testing for the preaction system passed inspection.
|
INSP-Sprinkler Rough-in/Hydro | 5/2/2007 | 5/2/2007 | 5/2/2007 | P | PART |
Forrest France
|
|
|
Begin air test 2:35 pm @ 52psi. as marked on guage.
|
INSP-Sprinkler Rough-in | 5/1/2007 | 5/2/2007 | 5/2/2007 | A | PART |
Forrest France
|
|
|
OH installation is acceptable, hydrostatic test of the preaction system completed, noted changes at preaction riser including drain termination point, different PRV than what is submitted, riser trim has been modified to include a potter ps40 in lieu of the mfg. supplied pressure switch.
|
Inspection Record Card- Fire | 4/6/2007 | | 4/6/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/6/2007 | | DONE |
|
|
|
|
Telephone call | | | 4/6/2007 | | |
|
|
|
lft vm with Jeff Anderson that permit and fees are ready to be picked up
|
Issue and Print Permit | | | 4/6/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/15/2007 | | 4/4/2007 | | PASS |
|
|
|
*Plans are approved as Submitted by Bryan Johnson
|
Miscellaneous action | | | 3/30/2007 | | DONE |
|
|
|
Approved an early start request to begin modification of existing wet system and installation of a preaction system per submitted plans; subject to condition to advise the FD of any impairment periods over 8 hours in duration At ###-####. Document attached.
|
Case Summary | | | 3/15/2007 | | |
|
|
|
|
Application received | | | 3/15/2007 | | |
|
|
|
|
Pending Assignment by SAM | 3/15/2007 | | | | |
|
|
|
|