Case Summary | | | 5/13/2008 | | DONE |
|
|
|
|
INSP-Final Inspection | 5/21/2007 | 5/21/2007 | 5/21/2007 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 5/17/2007 | 5/21/2007 | 5/21/2007 | A | FAIL |
Troy Cobbley
|
|
|
No access to tenant but I could see there were no canopies on the pendant heads. Inspection failed.
|
INSP-Sprinkler Rough-in | 4/30/2007 | 5/1/2007 | 5/1/2007 | A | PASS |
Troy Cobbley
|
|
|
Sprinkler piping is ok to cover
|
INSP-Sprinkler Rough-in | 4/26/2007 | 4/27/2007 | 4/27/2007 | A | FAIL |
Troy Cobbley
|
|
|
Pendant heads exceed the original design of 120sq/ft. Infact they exceed 130 sq/ft allowed for ordinary hazard. The existing upright heads are spaced at 165 sq/ft along the west wall and the piping to the pendants is hung from the bottom cord of the trusses. Uprights will need to be added and the hangers moved to the top of the truss or provide documentation that they can be hung from the bottom as discussed.
|
Issue and Print Permit | | | 4/23/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/19/2007 | | 4/19/2007 | | PASS |
|
|
|
Plan resubmittals passed
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/19/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/19/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/19/2007 | | 4/19/2007 | | DONE |
|
|
|
|
Telephone call | | | 4/19/2007 | | DONE |
|
|
|
left msg on vm for lillie, permit ready to p/u and fee is $379.38
|
Plan resubmittals received | | | 4/17/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/4/2007 | | 4/4/2007 | | DONE |
|
|
|
|
Telephone call | | | 4/4/2007 | | DONE |
|
|
|
t/c w lillie at shilo ###-#### - permit ready and fees given ($229.38)
|
Permit Ready to Issue | | | 4/4/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/4/2007 | | DONE |
|
|
|
|
Application received | | | 3/29/2007 | | |
|
|
|
|
Pending Assignment by SAM | 3/29/2007 | | | | |
|
|
|
|