INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 | A | PASS |
Forrest France
|
|
|
Required corrections verified for compliance, fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 7/25/2007 | 7/25/2007 | 7/25/2007 | A | PART |
Forrest France
|
|
|
Preaction system passed 24 hr. air test.
|
INSP-Sprinkler Rough-in/Hydro | 7/23/2007 | 7/24/2007 | 7/24/2007 | A | PART |
Forrest France
|
|
|
Begin 24 hr. air testing of the preaction system at 10:20 @ 40 psig.
|
INSP-Sprinkler Rough-in/Hydro | 7/20/2007 | 7/23/2007 | 7/23/2007 | A | PART |
Forrest France
|
|
|
OH hydrostatic test completed satisfactory, need to provide seismic clearance for the 6" main as indicated on approved plans, one upright head is installed too low.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/18/2007 | | DONE |
|
|
|
|
Telephone call | | | 4/18/2007 | | DONE |
|
|
|
tlk to jim darr ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 4/18/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/18/2007 | | 4/18/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/18/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/29/2007 | | 4/17/2007 | | PASS |
|
|
|
Plans are approved with Conditions by Bryan Johnson
|
Application received | | | 3/29/2007 | | |
|
|
|
|
Pending Assignment by SAM | 3/29/2007 | | | | |
|
|
|
|