Permit Information
Permit NumberFIR07-00285
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2501 N BOGUS BASIN RD
Project NameHEALTHWISE
Customer Number 
ePlanReview 
Description
Original Scope of Work:
Install a wet pipe system to serve through out the new structure. The systems will consist of a wet preaction riser and an anti-freeze loop to serve the exterior canopy. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-02598 & UG permit #FIR07-00364.
Original Plan Review Comments:5th Plan Review Comments 08/16/07:
The plans were resubmitted due to modifications in the field. The modifications were apparent TI changes which exposed un-sprinklered areas. The modifications were made with-in the remote area of operation which adversely affected the calculations. This revision is noted to be Rev. # 3 dated 07/13/07. All changes are clouded and noted on sheets FP-1 & 2. Calc area #2 summary appears to be correct.5th Plan Review Comments 08/16/07:
1. The plans were resubmitted due to modifications in the field. The modifications were apparent TI changes which exposed un-sprinklered areas. The modifications were made with-in the remote area of operation which adversely affected the calculations. This revision is noted to be Rev. # 3 dated 07/13/07. All changes are clouded and noted on sheets FP-1 & 2. Calc area #2 summary appears to be correct.Original Scope of Work:
Install a wet pipe system to serve through out the new structure. The systems will consist of a wet preaction riser and an anti-freeze loop to serve the exterior canopy. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-02598 & UG permit #FIR07-00364.
10/15/07 6th Plan Review Comments:
1. These As-Built plans were resubmitted due to modifications in the field. The modification adversely affects remote area 2 which required a complete resubmittal. Four additional heads were installed to accommodate the modifications. The Anti-freeze loop expansion chamber has been moved to the exterior of the bldg. The revision is noted to be Rev. #4, dated 10/04/07 FP-2 of 2.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/16/200710/18/200710/18/2007APASS
DetailsTroy Cobbley
permit finaled
PLANS/APPL TAKEN TO FRONT DESK  10/17/2007 DONE
Inspection Record Card- Fire10/17/2007 10/17/2007 DONE
Permit Ready to Issue  10/17/2007 DONE
Telephone call  10/17/2007 DONE
lft vm with lilly ###-#### that permit and fees are ready to be picked up
(F) Reprint permit  10/17/2007 DONE
CHANGE STATUS TO (ISS)  10/17/2007 DONE
INSP-Final Inspection10/12/200710/15/200710/15/2007PFAIL
DetailsForrest France
Provide forward flow bypass as indicated on approved plans, preaction pressure switch is not connected to the outside bell, need 911 sign at bell, provide lockout for the switches to the air compressor, need to certify the DCVA and the RP, provide calc. stickers, tags, signage etc. at the riser, need signage and locks for the control valves at the antifreeze loop, provide as-builts for field changes, need final walkthrough completed.
Sprinkler Plan Check10/8/2007 10/15/2007 PASS
Plans are approved with conditions by Bryan Johnson
Plan resubmittals received  10/8/2007  
received "5" books & "5" sets of plans including FP1 of 2 & FP2 of 2--plans put on shelf for fire
INSP-Sprinkler Rough-in9/20/20079/21/20079/21/2007APART
DetailsForrest France
Noted correction items from the previous inspection are complete, OH rough-in is acceptable.
INSP-Sprinkler Rough-in9/10/20079/11/20079/11/2007PFAIL
DetailsForrest France
See approved plans for areas in need of correction including overspacing at the data room, obstructed head at the second floor mech room, need to add one head in the riser room, blocked SW heads as noted, the antifreeze loop is not yet installed.
INSP-Sprinkler Rough-in/Hydro9/7/20079/10/20079/10/2007PPART
DetailsForrest France
OH hydrostatic test for the wet system and the preaction system both passed, contractor also completed a satisfactory UG supply line hydro as well.
Plan assigned to (SAM)8/3/2007 8/21/2007 PASS
8/21/2007 12:27:04 CMC - activity updated through activity FIRA22 from case FIR07-00285.
PLANS/APPL TAKEN TO FRONT DESK  8/21/2007 DONE
Inspection Record Card- Fire8/21/2007 8/21/2007 DONE
Telephone call  8/21/2007  
tlk to lilly ###-#### that permit and no fee ready to be picked up
Permit Ready to Issue  8/21/2007 DONE
CHANGE STATUS TO (ISS)  8/21/2007  
already issued
Sprinkler Plan Check8/2/2007 8/17/2007 PASS
Plans are approved by Bryan Johnson
Plan resubmittals received  8/2/2007  
Received five binders with applications and submittal info, and five copies of plan pages FP1, FP2; taken to fire review
INSP-Sprinkler Rough-in7/20/20077/23/20077/23/2007AFAIL
DetailsForrest France
Inspection for the 1st floor hard lid ceilings only, pendent head at the NW entry does not meet requirements of NFPA 13 table 8.6.5.1.2, heads at the restrooms and the elevator equip. room are okay for cover.
INSP-Supply line flush7/13/20077/16/20077/16/2007APART
DetailsForrest France
UG fire supply line flush completed satisfactory, circled on approved plans areas okay for cover on the 2nd floor, discussed coverage below stairs at the NW entry.
INSP-Sprinkler Rough-in7/11/20077/12/20077/12/2007APART
DetailsForrest France
Heads and piping at the 2nd floor stairway and restroom hard lid ceilings appears satisfactory, however no approved plans were made available on site for verification.
PLANS/APPL TAKEN TO FRONT DESK  6/26/2007 DONE
Inspection Record Card- Fire6/26/2007 6/26/2007 DONE
Inspection Record Card- Fire6/26/2007 6/26/2007 DONE
Telephone call  6/26/2007 DONE
tlk to lilly that her permit and fees are ready to be picked up
Permit Ready to Issue  6/26/2007  
Issue and Print Permit  6/26/2007 DONE
Sprinkler Plan Check6/15/2007 6/25/2007 PASS
Plans are approved by Bryan Johnson
Plan resubmittals received  6/15/2007  
re-submittals received - 5 fire sprinkler shop drawings , 5 calcs and data sent to fire/Scott A.
Plan resubmittals received  6/1/2007  
Plan resubmittals received  4/30/2007  
Telephone call  4/17/2007  
tlk to lily to let her know the quick permit has been denied
Plan resubmittals received  4/12/2007  
Case Summary  4/2/2007 DONE
Application received  4/2/2007  
Pending Assignment by SAM4/2/2007    