Permit Information
Permit NumberFIR07-00316
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 6401 S EISENMAN RD
Project NameQUARRY BUSINESS PARK CONDOS
Customer Number 
ePlanReview 
Description
Scope of Work:
Install 520’ of 6 C-900 Under Ground piping beginning from a 6” Gate valve located in the street at Eisenmen Road. A new hydrant will be installed at the west end of the new structure.
The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire “Inspection Card” are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD07-00349.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/16/200710/17/200710/17/2007APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/1/200710/4/200710/5/2007PCANC
DetailsForrest France
bill Phone #: ###-#### Incorrect permit number called in, was intended for the project related fire alarm permit.
INSP-Sprinkler Rough-in/Hydro9/19/20079/20/20079/20/2007APASS
DetailsForrest France
UG fire supply line passed hydrostatic testing.
INSP-Sprinkler Rough-in/Hydro9/14/20079/14/20079/14/2007PFAIL
DetailsForrest France
UG fire supply line hydro failed due to pressure loss at the guage.
INSP-Sprinkler Rough-in/Hydro9/12/20079/13/20079/13/2007AFAIL
DetailsForrest France
UG lost 15 psi. at the guage.
INSP-Supply line flush8/15/20078/15/20078/15/2007PPART
DetailsForrest France
UG fire supply line flush completed satisfactory.
INSP-Sprinkler Rough-in/Hydro8/10/20078/13/20078/13/2007AFAIL
DetailsForrest France
UG hydrostatic test failed due to pressure drop below 200 psi, guage appears damaged and may need to be replaced for accurate readings.
INSP-Sprinkler Rough-in/Hydro8/9/20078/10/20078/10/2007AFAIL
DetailsForrest France
UG fire supply line hydrostatic test failed due to 15psi. pressure loss at the guage.
Case Summary  7/26/2007  
INSP-Sprinkler Rough-in6/26/20076/27/20076/27/2007ACANC
DetailsForrest France
Per phone call from contractor, UG inspection canceled.
INSP-Sprinkler Rough-in6/20/20076/20/20076/21/2007PNR
DetailsForrest France
Work is not ready for inspection.
Issue and Print Permit  5/15/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  4/19/2007 DONE
Inspection Record Card- Fire4/19/2007 4/19/2007 DONE
Telephone call  4/19/2007  
tlk to brook ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  4/19/2007  
Sprinkler Plan Check4/10/2007 4/18/2007 PASS
Plans are approved w/attached Comments by Bryan Johnson
Case Summary  4/10/2007 DONE
Application received  4/10/2007  
Pending Assignment by SAM4/10/2007