Permit Information
Permit NumberFIR07-00333
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 1112 W MAIN ST Unit: 3RD FLR
Project NameROYAL PLAZA
Customer NumberRP 3 & 4
ePlanReview 
Description
This fire alarm permit is to complete the fire alarm system requirements in the common corridors of the associated 3rd and 4th floors. Building Permit BLD06-03304 is to construct a 1,292 square foot 1-hr fire-resistance-rated egress corridor to serve residential condominium units located on the 3rd story of a high-rise building. Work is to include 1-hr fire-resistance-rated corridor walls, corridor doors having a fire-protection-rating of 20 minutes, suspended ceilings, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/7/200712/7/200712/7/2007PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Alarm Testing12/6/200712/6/200712/6/2007PPASS
DetailsForrest France
Final pending NFPA 72 forms.
INSP-Final Inspection12/5/200712/5/200712/5/2007PPART
DetailsForrest France
Corrections have been verified, okay for final when shell and core alarm permit is finaled.
INSP-Final Inspection12/3/200712/4/200712/4/2007AFAIL
DetailsForrest France
The door closure at the trash chute is not properly adjusted.
INSP-Final Inspection11/27/200711/28/200711/28/2007ADEFR
DetailsForrest France
See inspection comments per M. Timmerman.
Inspection11/28/2007 11/28/2007PPART
DetailsMichael Timmerman
Inspection of Fire Alarm Devices on 3rd Floor and 4th Floor Corridor, Trash Bin Door Springs need to be Tightened to Close Properly and Latch. All Other Fire Alarm Devices Tested OK.
INSP-Final Inspection11/26/200711/27/200711/27/2007ACANC
DetailsForrest France
Overbooked.
INSP-Alarm Testing11/26/200711/26/200711/26/2007PDEFR
DetailsForrest France
Inspection request intended for the shell and core alarm work, items tested today include fire sprinkler monitoring of the fire pump, controller, power supplies, dry system, tampers, flows, etc. Outside bell does not function at pump flow switch, need 12 ah batteries at the FACP, tamper at the standpipe control valve is not correct.
FIR-Aging Inspection10/24/200710/24/200710/24/2007 DEFR
DetailsForrest France
work in progress
Issue and Print Permit  5/22/2007 DONE
Telephone call  4/17/2007  
tlk to receptionist lea electric ###-#### that permit and fees are ready to be picked up
Plan assigned to (Mike)4/10/2007 4/16/2007 PASS
4/16/2007 12:43:31 MWT - activity updated through activity FIRA22 from case FIR07-00333.
Alarm Plan Check4/16/2007 4/16/2007 PASS
Fire Alarm Review 2nd
PLANS/APPL TAKEN TO FRONT DESK  4/16/2007  
Ready for Issue
Inspection Record Card- Fire4/16/2007 4/16/2007 DONE
Permit Ready to Issue  4/16/2007  
Alarm Plan Check4/13/2007 4/13/2007 FAIL
Failed because it was submitted with tenant space floor plans that failed.
Miscellaneous action  4/13/2007  
Faxed copy of review to Lea Electric and Protex
Application received  4/10/2007