INSP-Final Inspection | 12/7/2007 | 12/7/2007 | 12/7/2007 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 12/6/2007 | 12/6/2007 | 12/6/2007 | P | PASS |
Forrest France
|
|
|
Final pending NFPA 72 forms.
|
INSP-Final Inspection | 12/5/2007 | 12/5/2007 | 12/5/2007 | P | PART |
Forrest France
|
|
|
Corrections have been verified, okay for final when shell and core alarm permit is finaled.
|
INSP-Final Inspection | 12/3/2007 | 12/4/2007 | 12/4/2007 | A | FAIL |
Forrest France
|
|
|
The door closure at the trash chute is not properly adjusted.
|
INSP-Final Inspection | 11/27/2007 | 11/28/2007 | 11/28/2007 | A | DEFR |
Forrest France
|
|
|
See inspection comments per M. Timmerman.
|
Inspection | 11/28/2007 | | 11/28/2007 | P | PART |
Michael Timmerman
|
|
|
Inspection of Fire Alarm Devices on 3rd Floor and 4th Floor Corridor, Trash Bin Door Springs need to be Tightened to Close Properly and Latch. All Other Fire Alarm Devices Tested OK.
|
INSP-Final Inspection | 11/26/2007 | 11/27/2007 | 11/27/2007 | A | CANC |
Forrest France
|
|
|
Overbooked.
|
INSP-Alarm Testing | 11/26/2007 | 11/26/2007 | 11/26/2007 | P | DEFR |
Forrest France
|
|
|
Inspection request intended for the shell and core alarm work, items tested today include fire sprinkler monitoring of the fire pump, controller, power supplies, dry system, tampers, flows, etc. Outside bell does not function at pump flow switch, need 12 ah batteries at the FACP, tamper at the standpipe control valve is not correct.
|
FIR-Aging Inspection | 10/24/2007 | 10/24/2007 | 10/24/2007 | | DEFR |
Forrest France
|
|
|
work in progress
|
Issue and Print Permit | | | 5/22/2007 | | DONE |
|
|
|
|
Telephone call | | | 4/17/2007 | | |
|
|
|
tlk to receptionist lea electric ###-#### that permit and fees are ready to be picked up
|
Plan assigned to (Mike) | 4/10/2007 | | 4/16/2007 | | PASS |
|
|
|
4/16/2007 12:43:31 MWT - activity updated through activity FIRA22 from case FIR07-00333.
|
Alarm Plan Check | 4/16/2007 | | 4/16/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/16/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 4/16/2007 | | 4/16/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/16/2007 | | |
|
|
|
|
Alarm Plan Check | 4/13/2007 | | 4/13/2007 | | FAIL |
|
|
|
Failed because it was submitted with tenant space floor plans that failed.
|
Miscellaneous action | | | 4/13/2007 | | |
|
|
|
Faxed copy of review to Lea Electric and Protex
|
Application received | | | 4/10/2007 | | |
|
|
|
|