Permit NumberFIR07-00338
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 4313- 4315 W ALBION
Project Name4313 & 4315
Customer Number 
ePlanReview 
Description
Scope of Work
Beginning from the supply side of the Back Flow Device, (Supplied By Others). Install a life safety modified NFPA 13D system in a new one story duplex. 2,426-ft/2. (Units 4313 & 4315 Combined). The modification is the installation of a single row of dry sidewall sprinklers along the common wall attached to the garage and the living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD06-03388.08/28/07 Revised Scope of Work
This plan review is a result of changes made in the field during construction that warranted a complete resubmittal including a revised set of calculations. A new riser location has been noted on the plans dated 08/09/07 noted as Revision #1.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/30/20081/31/20081/31/2008APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in9/6/20079/7/20079/7/2007APASS
DetailsTroy Cobbley
Some tenting modification was required but is now ok to cover
CHANGE STATUS TO (ISS)  9/7/2007  
issued previously
Inspection Record Card- Fire9/6/2007 9/6/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  9/6/2007  
Telephone call  9/6/2007 DONE
tlk to jim danes ###-#### that permit and no fees are ready to be picked up
Permit Ready to Issue  9/6/2007 DONE
Plan assigned to (SAM)8/14/2007 9/6/2007 PASS
9/6/2007 14:56:08 CMC - activity updated through activity FIRA22 from case FIR07-00338.
Sprinkler Plan Check8/14/2007 8/30/2007 PASS
Plans are approved by Bryan Johnson
Plan resubmittals received  8/14/2007  
Received five binders with one application and five copies of page FP1, FP2; taken to fire review
INSP-Sprinkler Rough-in/Hydro7/31/20078/1/20078/1/2007AFAIL
DetailsTroy Cobbley
The plans do not match the installation. For example the riser has been relocated 15' south and two additional rooms have been added to the building which will cause the remote area to be moved to the south. The backflow device installed is not what was submitted. Additional hangers are required. The riser has been installed as cpvc and does not meet the installation requirements of cpvc installation. The plans show the riser to be sch 40 galv. Plans need to be resubmitted. I only looked at the south most building before stopping the inspection
Issue and Print Permit  4/27/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  4/26/2007 DONE
Telephone call  4/26/2007  
lft vm with jim danes ###-#### that permit and fees are ready to be picked up
Inspection Record Card- Fire4/26/2007 4/26/2007 DONE
Permit Ready to Issue  4/26/2007 DONE
Sprinkler Plan Check4/11/2007 4/24/2007 PASS
Plans are approved by Bryan Johnson
Case Summary  4/11/2007 DONE
Application received  4/11/2007  
Pending Assignment by SAM4/11/2007