INSP-Final Inspection | 5/22/2007 | 5/22/2007 | 5/22/2007 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 5/11/2007 | 5/14/2007 | 5/14/2007 | P | PASS |
Forrest France
|
|
|
Corrections are complete, final FS inspection passed.
|
INSP-Sprinkler Rough-in | 5/9/2007 | 5/10/2007 | 5/10/2007 | A | FAIL |
Forrest France
|
|
|
Mixed temp. heads in the same fire areas, some heads exceed allowable distance below the ceiling, several heads need to be replaced due to visible corrosion at the seat.
|
Application received | | | 4/19/2007 | | |
|
|
|
|
Sprinkler Plan Check | 4/19/2007 | | 4/19/2007 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/19/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/19/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/19/2007 | | 4/19/2007 | | DONE |
|
|
|
|
Telephone call | | | 4/19/2007 | | DONE |
|
|
|
call to gerald w/ debest, permit ready to p/u and fee is $150
|
Issue and Print Permit | | | 4/19/2007 | | DONE |
|
|
|
|
Pending Assignment by SAM | 4/19/2007 | | | | |
|
|
|
|