Permit Information
Permit NumberFIR07-00380
StatusFinaled
Name LAYTON CONSTRUCTION
Site Address 7200 W BARRISTER DR
Project NameAda County Jail Medical Unit
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new fire alarm system in the new ADA County Jail Medical Facility and network this panel into the new FACP into the existing main jail central control fire alarm panel. The new fire alarm system includes area smoke detection, partial audible visual notification, smoke control and initiation, remote annunciator, sprinkler and HVAC duct detector monitoring. Building Permit BLD06-03515 is to construct a new 24,605 square foot, one story, masonry and steel framed Jail Medical Unit and Office building and related site improvements. This building is considered a new stand alone building with the Sally Port constructed to comply as a pedestrian walkway. All construction shall be per the approved plans and attached comment list. JCM

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/7/200711/8/200711/9/2007APASS
DetailsTroy Cobbley
Permit is ok to final per Mike Timmerman.
Inspection11/8/200711/8/200711/8/2007PPASS
Fire Alarm Corrections Check. Remaining 2 Items on the Medical Unit Corrections List Have Been Satisfactorly Completed. Troy Notified and Told to Final the Fire Alarm Permit.
INSP-Final Inspection10/29/200710/30/200710/31/2007PFAIL
DetailsTroy Cobbley
See mike timmermans notes for items tested and corrections needed.
Miscellaneous action  10/31/2007 DONE
Received request for fire approval for TOC from Mike Lakey emailed 10/31/07, based on latest outstanding FA issues. Request approved by D. Haneman; Fire is okay for temporary occupancy. DOC attached. Signed permit card on site, they will call for Bldg inspection tomorrow.
Inspection10/30/200710/30/200710/30/2007AFAIL
Inspection at Medical Unit Addition Verifying Correction Items;
1. A Duct Detector found improperly mounted in a previous inspection "Waiting Area" was changed to an In-Duct Detector. The new in-duct detector works correctly. Holes need to be patched in the duct work where old duct detector was removed.
2. The Smoke Control Sequence has changed significantly from the original proposed design. Provide a new sequence of operation and all necessary control functions and damper status at the Central Control Room FACP used as the Smoke Control Panel.
INSP-Final Inspection10/25/200710/26/200710/26/2007AFAIL
DetailsTroy Cobbley
The strobes now shutdown with the horns but the smoke control system still has issues. One duct smoke detector was found to be mounted incorrectly and is in the process of being fixed.
INSP-Alarm Testing10/23/200710/25/200710/26/2007AFAIL
DetailsTroy Cobbley
Need the smoke control system approved and the strobes to cease when the silence button is activated.
Inspection10/26/200710/26/200710/26/2007AFAIL
Witness Smoke Control acceptance by 3rd party engineer Jerry O'Neal, could not get desired differentials between smoke zone and corridor, while I was there. Also damper & position indication was not functional at the central control room. One duct detector needs to be relocated for proper operation.
INSP-Alarm Testing10/22/200710/25/200710/25/2007ACANC
DetailsTroy Cobbley
Duplicate inspection for today.
Inspection10/25/200710/25/200710/25/2007APART
Inspection; Corrections to be Made From Inspection conducted on 10-25-2007
1.) Deactivate Visual Notification with Audible
2.) Witness Smoke Control Cirtification

Verify correction items found 10-23-2007 -
1.) Supervision of Future Flow & Tamper Switches in Riser Room "Complete" MWT
2.) Provide As-Built Plans with Added Devices and Address Corrections "Provided" MWT
3.) Provide additional Detector Coverage in Day Rooms to with in 21' of corners. "Devices Added OK" MWT
4.) Provide missing Smoke Detector in Room 57. " Installed" MWT
INSP-Alarm Testing10/23/200710/23/200710/23/2007PFAIL
DetailsTroy Cobbley
See the city approved plans for the devices tested and the deficencies found. Also still need to test a/v's
Alarm Plan Check5/30/2007 5/31/2007 PASS
Resubmittal Review
PLANS/APPL TAKEN TO FRONT DESK  5/31/2007  
Ready for Issue
Permit Ready to Issue  5/31/2007 DONE
Inspection Record Card- Fire5/31/2007 5/31/2007 DONE
Telephone call  5/31/2007 DONE
left vm for terry moreau permit ready to pu. no fee
CHANGE STATUS TO (ISS)  5/31/2007 DONE
no fee due
Plan assigned to (Mike)4/25/2007 5/31/2007 PASS
5/31/2007 10:27:50 MWT - activity updated through activity FIRA22 from case FIR07-00380.
Plan resubmittals received  5/25/2007  
Received application and two copies of FA1, FA2, FA3, parts list, cut sheets, wire, calculations; taken to fire review
Telephone call  5/10/2007 DONE
call to Terry Moreau, will p/u application for resub on mon 5/14
Telephone call  5/10/2007  
Called Fire Alarm Vendor, Terry Moreau, Told Terry that the Project has problems with exiting in the B Occupancy areas and Cannot be resolved without a resubmittal to the building department. I had to fail the plans
Miscellaneous action  5/3/2007  
Fax copy of review to fire alarm vendor, Terry Moreau, ECS
(509)-###-####
Telephone call  5/3/2007  
Called Architect at CSHQA John Maulin ###-#### With questions on occupancy and the detention hardware. I dont knbow how to treat this submittal as submitted.
Alarm Plan Check5/1/2007 5/2/2007 FAIL
Fire Alarm Review 1st
Miscellaneous action  5/2/2007  
Fax Preliminary Review to Fire Alarm Installer. We have Issues with this fire alarm plan, waiting for response from Sam.
Application received  4/25/2007