Permit Information
Permit NumberFIR07-00392
StatusFinaled
Name ROMAR ELECTRIC
Site Address 1111 W JEFFERSON ST Unit: 550
Project NameBOISE - 1111 W JEFFERSON
Customer Number 
ePlanReview 
Description
This permit is to add audible visual notification appliances in a new 5th floor tenant space and a new exit corridor that leads to the exit stairwells. Building permit BLD07-00842 is the Interior remodel for a new 9,683 sq. ft. office tenant in the northwest corner of the 5th floor of an existing high-rise building per approved plans. Work to include some miscellaneous interior demolition work, new interior walls, new interior doors and windows, interior finish, counters/casework, new suspended ceiling, fire sprinkler and alarm work, mechanical work, plumbing work, and electrical work. Work will include a common core hallway/non-rated corridor connecting to the north and south exit stairs on the west half of the building. A Certificate of Occupancy is to be issued when completed and approved. NOTE: This building will be fully fire sprinklered by March of 2011 per an Upgrade Agreement on file. JCB
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/30/20077/30/20077/30/2007PPASS
DetailsForrest France
Corrections are complete, fire alarm permit finaled.
INSP-Final Inspection7/27/20077/27/20077/27/2007PFAIL
DetailsForrest France
Mag locks at two doors failed to drop out upon FA activation.
INSP-Final Inspection7/25/20077/26/20077/26/2007PFAIL
DetailsForrest France
Two SD did not function upon testing, interconnection for the access control egress mag locks are not complete. AV notification and two manual pull stations tested satisfactory.
Issue and Print Permit  5/7/2007 DONE
Plan assigned to (Mike)4/30/2007 5/3/2007 PASS
5/3/2007 14:43:20 MWT - activity updated through activity FIRA22 from case FIR07-00392.
Alarm Plan Check5/2/2007 5/3/2007 PASS
Fire Alarm Review 1st
Telephone call  5/3/2007  
Called Romar and Nelson Fire Systems about missing data for the booster calculations and the voltage drop. They are going to fax the information to me.
PLANS/APPL TAKEN TO FRONT DESK  5/3/2007  
Ready for Issue
Permit Ready to Issue  5/3/2007 DONE
Inspection Record Card- Fire5/3/2007 5/3/2007 DONE
Telephone call  5/3/2007 DONE
left msg on sandi's vm, permit ready to p/u fee $150
Application received  4/30/2007  
Case Summary  4/30/2007