INSP-Final Inspection | 7/30/2007 | 7/30/2007 | 7/30/2007 | P | PASS |
Forrest France
|
|
|
Corrections are complete, fire alarm permit finaled.
|
INSP-Final Inspection | 7/27/2007 | 7/27/2007 | 7/27/2007 | P | FAIL |
Forrest France
|
|
|
Mag locks at two doors failed to drop out upon FA activation.
|
INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 | P | FAIL |
Forrest France
|
|
|
Two SD did not function upon testing, interconnection for the access control egress mag locks are not complete. AV notification and two manual pull stations tested satisfactory.
|
Issue and Print Permit | | | 5/7/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 4/30/2007 | | 5/3/2007 | | PASS |
|
|
|
5/3/2007 14:43:20 MWT - activity updated through activity FIRA22 from case FIR07-00392.
|
Alarm Plan Check | 5/2/2007 | | 5/3/2007 | | PASS |
|
|
|
Fire Alarm Review 1st
|
Telephone call | | | 5/3/2007 | | |
|
|
|
Called Romar and Nelson Fire Systems about missing data for the booster calculations and the voltage drop. They are going to fax the information to me.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/3/2007 | | |
|
|
|
Ready for Issue
|
Permit Ready to Issue | | | 5/3/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/3/2007 | | 5/3/2007 | | DONE |
|
|
|
|
Telephone call | | | 5/3/2007 | | DONE |
|
|
|
left msg on sandi's vm, permit ready to p/u fee $150
|
Application received | | | 4/30/2007 | | |
|
|
|
|
Case Summary | | | 4/30/2007 | | |
|
|
|
|