Case Summary | | | 12/5/2016 | | DONE |
|
|
|
|
Final inspection | | | 11/27/2007 | | PASS |
|
|
|
This Entry Was Made To Put The Permit in Final Status - Troy Finaled this Permit
|
INSP-Final Inspection | 8/15/2007 | 8/15/2007 | 8/15/2007 | P | PART |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 7/26/2007 | 7/27/2007 | 7/27/2007 | A | FAIL |
Troy Cobbley
|
|
|
Relocate the smoke detectors 3' away from the ceiling fan blade tips, provide the required audio level at the pillows and sync the audio devices.
|
Issue and Print Permit | | | 5/23/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/23/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 5/3/2007 | | 5/18/2007 | | PASS |
|
|
|
5/18/2007 13:47:39 MWT - activity updated through activity FIRA22 from case FIR07-00419.
|
Alarm Plan Check | 5/18/2007 | | 5/18/2007 | | PASS |
|
|
|
Fire Alarm Review 2nd
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/18/2007 | | |
|
|
|
Ready for Issue
|
Permit Ready to Issue | | | 5/18/2007 | | DONE |
|
|
|
|
Telephone call | | | 5/18/2007 | | DONE |
|
|
|
call into daniel buccino, permit ready to p/u, fee $217.20
|
Inspection Record Card- Fire | 5/18/2007 | | 5/18/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/15/2007 | | |
|
|
|
received re-submittal fire alarm application, 2 cover sheet books,and 2 copys of sheets F.A.01 routed to Mike T . in fire
|
Alarm Plan Check | 5/11/2007 | | 5/11/2007 | | FAIL |
|
|
|
Fire Alarm Review 1st - Remove visual meeting with contractor
|
Telephone call | | | 5/11/2007 | | |
|
|
|
Called Fire Alarm Vendor Dan Buccino ###-#### Asked him to come in and identify rooms on the plans submitted.
|
Case Summary | | | 5/3/2007 | | |
|
|
|
|
Application received | | | 5/3/2007 | | |
|
|
|
|