Permit Information
Permit NumberFIR07-00441
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 10136 S FEDERAL WAY
Project NameMICRON NANOFAB
Customer Number 
ePlanReview 
Description
This permit is to install a new fire alarm system in a new memory chip manufacturing building (Micron Nanofab) The fire alarm system includes VESDA fire smoke detection. IT room, required manual fire alarm system, required automatic fire alarm detection, audible/visual notification, sprinkler and HVAC alarm monitoring, fire smoke dampers, elevator recall and shut down and offsite alarm supervision. Building Permit BLD06-03088 is to construct a new 112,315 square foot, three story, semiconductor fabrication facility and related site improvements. This building contains a fabrication area, support areas for the fabrication area, hazardous materials storage areas at the first floor and administrative office areas. 1st. Fl. (B Level) 28,715 sq. ft., 2nd. Fl. (Main Level) 61,150 sq. ft., 3rd. Fl. 22,450 sq. ft.. A partial footing and foundation permit was issued under BLD06-02671. All construction shall be per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/29/200711/30/200711/30/2007APASS
DetailsForrest France
Corrections verified, resubmittals for as-built plans accepted, final inspection passed. NFPA 72 record of completion forms to be delivered to PDS fire office today for signature as agreed.
Plan resubmittals received  11/29/2007  
Received two binders with applications and three copies of FA2.1, FA2.3, FA2.4, FA2.B, FA2.U, FA3.00, FA3.01; taken to fire review
Plan assigned to (Mike)11/29/2007 11/29/2007  
Resubmittal required by Field Inspector Major Changes
Alarm Plan Check11/29/2007 11/29/2007 PASS
DetailsMichael Timmerman
Resubmittal As-Built Review Conducted Due To So Many Field
Modification and Additional Devices Added. Compared As- Built Floor Plans, Riser and Calculations to Approved Plans Everything Changed Is In Compliance with Current NFPA72 Standard Installation Practices. No Written Documents Attached
PLANS/APPL TAKEN TO FRONT DESK  11/29/2007  
Ready for Re-Issue
Inspection Record Card- Fire11/29/2007 11/29/2007 DONE
Telephone call  11/29/2007 DONE
left vm for andy sellers at ###-#### - permit ready and fees given
Permit Ready to Issue  11/29/2007 DONE
CHANGE STATUS TO (ISS)  11/29/2007  
picked up approved resubmittals
Telephone call  11/8/2007  
Called Andy Sellers with Quality Electric left Msg that Forrest France is requiring a resubmittal due to the field changes made not just an As-Built. Told Andy that all changes from the approved plans would need to be clouded
INSP-Final Inspection10/25/200710/26/200710/26/2007APART
DetailsForrest France
Verified corrections have been completed, final pending resubmitted plans reflecting all field modifications.
INSP-Final Inspection10/25/200710/25/200710/25/2007PNH
DetailsForrest France
No access available to the areas in need of inspection.
INSP-Final Inspection10/23/200710/23/200710/23/2007PCANC
DetailsForrest France
Duplicate inspection request.
INSP-Final Inspection10/19/200710/22/200710/23/2007APART
DetailsForrest France
Tested cleanroom notification-noted two areas lacking sufficient visual coverage, need to program voltage monitoring at the elevator for a supervisory condition, retested c/n items from previous inspection.
INSP-Final Inspection10/18/200710/19/200710/19/2007APART
DetailsForrest France
Elevator testing completed, noted voltage monitoring to be supervisory, not an alarm condition as programed.
INSP-Alarm Testing10/5/200710/9/200710/9/2007ADEFR
DetailsForrest France
sandy Note:elevator Phone #: ###-####
Can be completed in conjunction with the remainder of the fire alarm work to be inspected ie. cleanroom areas.
INSP-Alarm Testing9/11/20079/11/20079/11/2007APART
DetailsForrest France
Tested units at the fan deck, some items on this level are not yet amended for reinspection, the horn at the roof level sheet FA 2.4 does not function, notification devices at the underfloor area tested acceptable, EOL at the office area retested okay after corrections. Noted fire alarm for the office area is now approved.
INSP-Alarm Testing9/11/20079/12/20079/11/2007ACANC
DetailsForrest France
Scheduled by a contractor via Hello! on 9/11/2007 at 7:10:04 AM. Contact: ###-####. Inspection cancelled from web by: Patricia Smith
INSP-Final Inspection9/7/20079/10/20079/10/2007APART
DetailsForrest France
Tested second floor fan deck areas, noted one SD in the electrical room to be added, two duct detectors are descripted incorrect, marked devices not yet ready for testing including the elevator and four duct detectors at units not currently running, discussed occupancy requirements with the general contractor for the office portion of the first floor.
INSP-Alarm Testing9/5/20079/7/20079/10/2007APART
DetailsForrest France
EOL voltage drop at the office area is too low, one SD in the electrical room has an incorrect descriptor, incorrect cd at the receiving area amended while on site, retested noted defficiencies from the previous visit, highlighted locations on the first floor not yet complete for inspection including the elevator and cleanroom areas, noted ECS room staff is lacking for constant attendance as only one trained employee is provided at this time.
INSP-Alarm Testing9/5/20079/6/20079/7/2007APART
DetailsForrest France
Reinspection for the first floor office area defficiencies, see approved plan set for locations tested today and items in need of correction including blocked strobe notification, incorrect descriptor at an electrical room smoke, SD at an electrical closet, noted ECS room is now staffed with trained personel.
INSP-Final Inspection8/31/20079/5/20079/6/2007APART
DetailsForrest France
Retested noted defficiencies at the basement level, see approved plans for first floor areas tested today, noted descriptor for the electrical room 101G reports a 101N, will need to retest one SD at the east corridor door hold release.
INSP-Final Inspection8/31/20079/4/20079/4/2007ANR
DetailsForrest France
sandy; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt
INSP-Final Inspection8/29/20078/30/20078/30/2007AFAIL
DetailsForrest France
See approved plans sheet FA1 for defficiencies at the south office area inspected today including several blocked horn/strobe notification devices at the open office 105 due to 80" high cubicle partitions, SD at the nac panels in the BCS room is too close to an air return grill, one blocked h/s at the file room due to cabinetry, one overspaced h/s at the west side of office 105, noted the ECS room is not staffed at this time and missing some required items per NFPA 72 ch. 8.
INSP-Final Inspection8/28/20078/29/20078/29/2007PCANC
DetailsTroy Cobbley
sandy Phone #: ###-####Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
INSP-Final Inspection8/27/20078/28/20078/28/2007AFAIL
DetailsForrest France
Tested remainder of devices on sheet FP2.1, noted locations on plan in need of correction including non-functional a/v devices, incorrect cd settings, blocked a/v, noted six duct detectors with the sample and vent tubes switched- need to install per mfg. recommendations or provide air flow test data.
INSP-Alarm Testing8/21/20078/27/20078/27/2007AFAIL
DetailsForrest France
See approved plans for areas inspected today, noted one H/S is blocked, one incorrect cd rating, switched address on the sprinkler PIV and forward flow tampers.
PLANS/APPL TAKEN TO FRONT DESK  8/16/2007  
Ready for Issue
Inspection Record Card- Fire8/16/2007 8/16/2007 DONE
Telephone call  8/16/2007  
lft ms for andy sellers ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  8/16/2007 DONE
Issue and Print Permit  8/16/2007 DONE
Plan assigned to (Mike)5/9/2007 8/16/2007 PASS
8/16/2007 11:05:37 MWT - activity updated through activity FIRA22 from case FIR07-00441.
Alarm Plan Check  8/15/2007 PASS
Fire Alarm Review 4th
Plan resubmittals received  8/8/2007  
Telephone call  7/20/2007  
Called fire alarm installing contractor Andy Sellers with Quality Electric told Andy that I will hold the data sheets while I wait for legible fire alarm drawings.
Telephone call  7/20/2007  
Fax Copy of 3rd review to Alarm Installing Contractor
Telephone call  7/18/2007  
Called applicant, Andy Sellers at Quality Electric (###-####), told Andy that the floor plan drawings received in resubmittal #2 the walls and room designations were way to light for us accept, again! The drawings were rejected for this once before. I am going to conduct the review, however, will not issue drawings until we receive an acceptable set of floor plans.
Alarm Plan Check  7/18/2007 FAIL
Fire Alarm Review 3rd
Telephone call  7/18/2007  
Called applicant, Andy Sellers again at Quality Electric (###-####), told Andy that the floor plans for level B most doors are not shown. Addressing has changed on several initiating devices again. Title Block, Direction Arrows, Scale, Key are missing on all Plans. I vented my frustration to Andy with their resubmitted fire alarm plans.
Telephone call  7/12/2007  
Called contractor to see where resubmital plans are! Still waiting for them here. Contractor, Andy Sellers said resubmittals are almost ready and is going to try and bring them down shortly. e-mailed my concern to Sam and Jenifer.
Plan resubmittals received  7/12/2007  
Telephone call  6/27/2007  
resubmittal required- gave plans to quality elec
Miscellaneous action  6/26/2007  
Faxed copy of Review to Andy Sellers Quality Electric ###-####
Telephone call  6/26/2007 DONE
left vm for andy sellers at quality electric ###-#### - permit needs to be picked up and resubmitted
Telephone call  6/21/2007  
Called Andy Sellers with Quality Electric ###-#### Told Andy the plans brought in were again the wrong scale I need to start the review. Plans I have are not legabile either.
Alarm Plan Check  6/19/2007 FAIL
Fire Alarm Review 2nd Waiting for Legible 1/8" Scale Drawings.
6-21-2007 Contractor brought in the wrong set of drawings I need to do the review. Still waiting on 1/8" Scaled, legible drawings that I can read. Received plans 6/21/2007 will begin review by Monday 6/25/2007
Telephone call  6/19/2007  
Called Andy Sellers with Quality Electric. Told Andy I need the 1/8 scaled drawings to be legible for review. Andy said he would get them to me ASAP!
Plan resubmittals received  6/15/2007  
Received application and two copies of specifications, battery calculations, voltage drop calcs, equipment submittals, early warning smoke detection submittals (VESDA), and drawings FA.1 (2 pgs.), FA.2 (2 pgs.), FA.3 (2 pgs.), FA.4 (2 pgs.), FA.5 (2 pgs.), FA3.00; taken to Mike Timmerman
Miscellaneous action  5/18/2007  
E-Mailed copy of failed fire alarm review to Andy Sellers Quality Electric and Brian Pepper at Micron
Alarm Plan Check  5/15/2007 FAIL
Fire Alarm Review 1st
Plan resubmittals received  5/10/2007  
Application received  5/9/2007