Permit NumberFIR07-00446
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 3662 S ECKERT RD
Project NameLucky 13 Restuarant
Customer Number 
ePlanReview 
Description
Scope of Work:
Fire sprinkler work is related to selective demolition, construction of new non-combustible interior partitions to create patient staging, observation and bi-plane lab, the installation of new suspended ceiling grid system per plans which may include red-lined notes, attached plan review conditions, regulated by the Fire Chief. This building is fully sprinklered and shall remain so. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD06-0.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-0. This permit is not attached to any other permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  8/11/2015 DONE
INSP-Final Inspection9/24/20079/24/20079/24/2007PPASS
DetailsForrest France
Fire sprinkler final inspection passed per K. Roule.
INSP-Sprinkler Rough-in/Hydro9/14/20079/17/20079/17/2007APART
DetailsForrest France
Overhead hydrostatic test for the two wet systems and the antifreeze loop passed, remainder of OH install is complete and corrections made, noted one pendent head to be changed to a 155 deg as discussed.
INSP-Sprinkler Rough-in8/10/20078/13/20078/13/2007PPART
DetailsForrest France
OH install is approved except as highlighted on approved plans for areas not completed including two stairways and the antifreeze loop, also noted one missing hanger on the 2nd floor, discussed WPI and FDC locations as well.
INSP-Sprinkler Rough-in8/9/20078/10/20078/10/2007ACANC
DetailsForrest France
Inspection rescheduled per phone call from contractor.
INSP-Supply line flush8/8/20078/8/20078/8/2007PPART
DetailsForrest France
UG supply line flush completed satisfactory.
INSP-Sprinkler Rough-in/Hydro8/8/20078/8/20078/8/2007PPART
DetailsForrest France
UG hydrostatic test passed within allowable limits per NFPA 13.
INSP-Sprinkler Rough-in/Hydro7/6/20077/6/20077/6/2007PCANC
DetailsTroy Cobbley
Can not perform inspection due to time constraints. Will have to be rescheduled.
INSP-Supply line flush7/6/20077/6/20077/6/2007PCANC
DetailsTroy Cobbley
Can not perform inspection due to time constraints. Will have to be rescheduled.
Issue permit  5/29/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  5/25/2007 DONE
Inspection Record Card- Fire5/25/2007 5/25/2007 DONE
Telephone call  5/25/2007 DONE
tlk to sam ball ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  5/25/2007 DONE
Sprinkler Plan Check5/11/2007 5/24/2007 PASS
Plans are approved by Bryan Johson
Case Summary  5/11/2007 DONE
Application received  5/11/2007  
Pending Assignment by SAM5/11/2007