Permit Information
Permit NumberFIR07-00461
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 6411 W FAIRFIELD AVE
Project NameMcKinley Elementary School
Customer Number 
ePlanReview 
Description
Scope of Work: Under Ground Only
Beginning from an existing 6” C900 line stubbed in from the street off of W. Fairfield Ave., continue the 6” out and stub up into the riser room of the new 59,007-ft/2 bldg. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire “Inspection Card” are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD07-00143.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  3/11/2009 DONE
Sent for archiving
INSP-Final Inspection1/26/20091/28/20091/28/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro3/25/20083/26/20083/26/2008APASS
DetailsTroy Cobbley
UG Hydro Inspection passed
INSP-Sprinkler Rough-in3/24/20083/25/20083/25/2008APASS
DetailsTroy Cobbley
UG Flush Passed
INSP-Sprinkler Rough-in3/20/20083/24/20083/24/2008AFAIL
DetailsTroy Cobbley
This inspection was for an underground flush. The contractor had set up the flush through a 2 1/2" hose. The system riser is 4". Without a pito guage the actual flow could not be verified so no flush was performed. The underground flush shall conform to NFPA 13 10.10.2.1.3.
INSP-Sprinkler Rough-in10/30/200710/31/200710/31/2007APASS
DetailsTroy Cobbley
The underground piping is ok to cover but the installation does not match the plans. Additional fitting have been added as well as additional piping. I'm contacting DeBest Fire about my concerns.
INSP-Sprinkler Rough-in7/3/20077/3/20077/3/2007PPASS
DetailsTroy Cobbley
5'0" underground stub out is ok to cover
PLANS/APPL TAKEN TO FRONT DESK  6/12/2007 DONE
Inspection Record Card- Fire6/12/2007 6/12/2007 DONE
Permit Ready to Issue  6/12/2007 DONE
Telephone call  6/12/2007 DONE
tlk to jim heiller ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  6/12/2007 DONE
Sprinkler Plan Check5/21/2007 6/6/2007 PASS
Plans are approved by Bryan Johnson
Case Summary  5/21/2007 DONE
Application received  5/21/2007  
Pending Assignment by SAM5/21/2007