Permit Information
Permit NumberFIR07-00472
StatusFinaled
Name PROTEX
Site Address 1112 W MAIN ST Unit: 5TH FLR
Project NameROYAL PLAZA
Customer NumberRP 6
ePlanReview 
Description
This fire alarm permit is to install smoke detection and fire alarm system notification appliances in a new 5th floor corridor at the Royal Plaza Building. Building Permit BLD06-03528 is to construct a 1,461 square foot 1-hr fire-resistance-rated egress corridor system to serve residential condominium units located on the 5th story of a high-rise building. Work is to include 1-hr fire-resistance-rated corridor walls, corridor doors having a fire-protection-rating of 20 minutes, suspended ceilings, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/25/2008 DONE
Plans sent to records for scanning.
INSP-Final Inspection1/22/20081/22/20081/22/2008PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Alarm Testing1/21/20081/22/20081/22/2008APASS
DetailsForrest France
Required corrections listed at the previous inspection verified for completion, fire alarm testing passed.
INSP-Final Inspection1/18/20081/18/20081/18/2008PFAIL
DetailsForrest France
Need to change descriptor for the smoke detector at the electrical closet, , damper at suite 504 did not close upon actuation of the ID detector, addresses at the in duct detectors for the shell and core devices between units 501 and 502 are not accurate (duplicated elsewhere).
FIR-Aging Inspection12/3/200712/3/200712/3/2007 DEFR
DetailsForrest France
wip
Issue and Print Permit  7/30/2007 DONE
Inspection Record Card- Fire7/27/2007 7/27/2007 DONE
Telephone call  7/27/2007 DONE
spoke w/rob @ protex and informed of permit ready and fees.
Permit Ready to Issue  7/27/2007 DONE
Alarm Plan Check7/26/2007 7/26/2007 PASS
Fire Alarm Review 2nd
PLANS/APPL TAKEN TO FRONT DESK  7/26/2007  
Ready for Issue
Telephone call  7/24/2007  
Called fire alarm vendor (Rob Ahten) at Protex. Let Rob know the floor plans for Royal Plaza are still unacceptable. Rob wants to come down & meet with me tomorrow 7/25/2007.
Plan resubmittals received  7/18/2007  
Recieved application, 2 copies of folders of submittal info, pages RP103A, RP106A, RPR1A, sequence of operation, battery calcs; taken to fire review
Plan assigned to (Mike)5/22/2007 5/31/2007 PASS
5/31/2007 14:43:58 CMC - activity updated through activity FIRA22 from case FIR07-00144.
Alarm Plan Check5/30/2007 5/30/2007 FAIL
Fire Alarm Review 1st
Miscellaneous action  5/30/2007  
Fax Copy of Review to Fire Alarm Vendor and Applicant
Application received  5/22/2007