INSP-Final Inspection | 10/30/2007 | 10/31/2007 | 10/31/2007 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
CHANGE STATUS TO (ISS) | | | 10/30/2007 | | DONE |
|
|
|
reopen flow switch was not hooked to the fire panel needs to be reopened
|
INSP-Final Inspection | 10/5/2007 | 10/8/2007 | 10/8/2007 | A | PASS |
Troy Cobbley
|
|
|
The hydro test on the new system passed and the overhead inspection passed except in the existing area/expansion needs three additional heads due to overspacing off of the wall.
|
INSP-Final Inspection | 10/1/2007 | 10/5/2007 | 10/5/2007 | A | FAIL |
Troy Cobbley
|
|
|
The hydro test above the check valve held pressure but between the check valve and the fdc did not hold pressure
|
Issue and Print Permit | | | 9/10/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/7/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/7/2007 | | 9/7/2007 | | DONE |
|
|
|
|
Telephone call | | | 9/7/2007 | | DONE |
|
|
|
tlk to brad bettencourt ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 9/7/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/13/2007 | | 8/27/2007 | | PASS |
|
|
|
Plans are approved by Bryan Johnson
|
Plan resubmittals received | | | 8/13/2007 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 8/6/2007 | 8/6/2007 | 8/6/2007 | P | FAIL |
Troy Cobbley
|
|
|
I inspected the two bays over the mezzanine and found that the hangers and trapeze members are the wrong size. This is the only area I inspected.
|
INSP-Sprinkler Rough-in | 8/1/2007 | 8/2/2007 | 8/3/2007 | P | PASS |
Troy Cobbley
|
|
|
This inspection was for the hanger attachment points that will soon be covered with insulation. The hanger attachments passed.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/29/2007 | | |
|
|
|
|
Inspection Record Card- Fire | 6/19/2007 | | 6/29/2007 | | DONE |
|
|
|
|
Telephone call | | | 6/29/2007 | | DONE |
|
|
|
tlk to brad bettencourt ###-#### that permit and -0- are ready to be picked up
|
Permit Ready to Issue | | | 6/29/2007 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 6/29/2007 | | |
|
|
|
already issued previously
|
(F) Reprint permit | | | 6/29/2007 | | |
|
|
|
|
Sprinkler Plan Check | 6/19/2007 | | 6/26/2007 | | PASS |
|
|
|
Revised Plans are approved by Bryan Johnson
|
Plan resubmittals received | | | 6/19/2007 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/15/2007 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 6/15/2007 | | |
|
|
|
|
Inspection Record Card- Fire | 6/15/2007 | | 6/15/2007 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 6/15/2007 | | |
|
|
|
|
Inspection Record Card- Fire | 6/15/2007 | | 6/15/2007 | | DONE |
|
|
|
|
Telephone call | | | 6/15/2007 | | DONE |
|
|
|
tlk to brad bettencourt ###-#### that permit and fees are ready to be picked up
|
Override - Parcel Holds | | | 6/15/2007 | | |
|
|
|
|
Permit Ready to Issue | | | 6/15/2007 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 6/15/2007 | | |
|
|
|
|
Issue and Print Permit | | | 6/15/2007 | | |
|
|
|
|
Sprinkler Plan Check | 5/24/2007 | | 6/12/2007 | | PASS |
|
|
|
Plans are approved with conditions per Bryan Johnson
|
Case Summary | | | 5/24/2007 | | DONE |
|
|
|
|
Application received | | | 5/24/2007 | | |
|
|
|
|
Pending Assignment by SAM | 5/24/2007 | | | | |
|
|
|
|
Pending Assignment by SAM | 8/13/2007 | | | | |
|
|
|
|