INSP-Final Inspection | 3/10/2008 | 3/10/2008 | 3/11/2008 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 11/2/2007 | 11/5/2007 | 11/5/2007 | P | PART |
Forrest France
|
|
|
OH hydrostatic testing passed.
|
INSP-Final Inspection | 8/10/2007 | 8/16/2007 | 8/16/2007 | P | NR |
Forrest France
|
|
|
Need completion of the OH hydrostatic tests and related riser supervision testing prior to final.
|
INSP-Sprinkler Rough-in/Hydro | 8/10/2007 | 8/16/2007 | 8/16/2007 | P | PART |
Forrest France
|
|
|
Verified corrections noted at the previous inspection have been completed, hydrostatic testing failed due to pressures below 200 psi at the guages.
|
INSP-Sprinkler Rough-in/Hydro | 8/7/2007 | 8/10/2007 | 8/10/2007 | P | DEFR |
Forrest France
|
|
|
Rescheduled per discussion with contractor.
|
INSP-Final Inspection | 8/7/2007 | 8/10/2007 | 8/10/2007 | P | NR |
Forrest France
|
|
|
Need to test sprinkler monitoring and alarm via project related FA permit prior to final approval.
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2007 | 7/30/2007 | 7/31/2007 | P | FAIL |
Forrest France
|
|
|
Provide longitudinal bracing for the 2.5" main as discussed, need to fire caulk new penetrations in existing rated walls, need to install intermediate temp. heads at the stairway skylights.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/20/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/20/2007 | | 6/20/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/20/2007 | | DONE |
|
|
|
|
Telephone call | | | 6/20/2007 | | DONE |
|
|
|
tlk to jim danes ###-#### that permit and fees are ready to be picked up
|
Issue permit | | | 6/20/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/25/2007 | | 6/18/2007 | | PASS |
|
|
|
Plans are approved by bryan johnson
|
Case Summary | | | 5/25/2007 | | DONE |
|
|
|
|
Application received | | | 5/25/2007 | | |
|
|
|
|
Pending Assignment by SAM | 5/25/2007 | | | | |
|
|
|
|