Permit Information
Permit NumberFIR07-00484
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 7701 NORTHVIEW
Project NameFairmont Park Elementary
Customer Number 
ePlanReview 
Description
Scope of Work: Under Ground Only
Beginning from an existing 6” C900 line stubbed in from the street off of W. Northview Street, continue the 6” out 146’ Lf. and stub up into the riser room of the new 57,367-ft/2 bldg. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire “Inspection Card” are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD06-03277.
Scheduling Inspections:
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/26/20086/26/20086/26/2008PPASS
DetailsForrest France
Under ground completed. As per Troys inspections.
CHANGE STATUS TO (ISS)  6/26/2008 DONE
Plan assigned to (SAM)2/14/2008 3/19/2008 PASS
DetailsCathy Brown
3/19/2008 09:05:16 CMB - activity updated through activity FIRA22 from case FIR07-00697.
Case Summary  2/19/2008  
Plan resubmittals received  2/14/2008  
received five copies of application, submittal package and plan sheets FP1, FP2, FP3; taken to fire review
INSP-Sprinkler Rough-in/Hydro1/29/20081/30/20081/30/2008PPASS
DetailsTroy Cobbley
The underground hydro test passed.
INSP-Sprinkler Rough-in7/5/20077/5/20077/5/2007PPASS
DetailsTroy Cobbley
The underground supply line is now ok to bury. The connection to united water still needs to be done.
INSP-Sprinkler Rough-in7/2/20077/3/20077/3/2007AFAIL
DetailsTroy Cobbley
The bury depth of the underground piping does not meet the minumum 4'6" bury depth. Since the next inspection will be the third I have applied a re-inspection fee
INSP-Sprinkler Rough-in6/29/20077/2/20077/2/2007AFAIL
DetailsTroy Cobbley
The underground supply piping has been covered with bedding. I can't see pipe size, tracer wire or the two additional thrust blocks that have been pored. Pipe needs to be uncovered.
PLANS/APPL TAKEN TO FRONT DESK  6/15/2007 DONE
Inspection Record Card- Fire6/15/2007 6/15/2007 DONE
Telephone call  6/15/2007 DONE
tlk to lillie scales ###-#### that permit is ready to be picked up and fees
Permit Ready to Issue  6/15/2007 DONE
Issue and Print Permit  6/15/2007 DONE
Sprinkler Plan Check5/29/2007 6/13/2007 PASS
Plans are approved by Bryan Johnson
Case Summary  5/29/2007  
Application received  5/29/2007  
Pending Assignment by SAM5/29/2007