INSP-Final Inspection | 11/16/2007 | 11/19/2007 | 11/19/2007 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 11/16/2007 | 11/16/2007 | 11/16/2007 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled, contractor to provide SW heads at the head box as agreed.
|
INSP-Sprinkler Rough-in/Hydro | 11/6/2007 | 11/7/2007 | 11/7/2007 | A | PART |
Forrest France
|
|
|
OH hydrostatic test passed, c/n items from the previous inspection have been completed, noted that no provision has been made at the riser for forward flow testing of the DCVA backflow.
|
INSP-Sprinkler Rough-in | 9/5/2007 | 9/6/2007 | 9/6/2007 | A | PART |
Forrest France
|
|
|
OH rough-in is approved except as noted or not yet complete-see annotations on stamped plan set including seismic clearance at a 4" riser, overspaced heads due to HVAC, missing head at the janitors room, SW at the overhead doors are not installed at this time.
|
INSP-Supply line flush | 8/28/2007 | 8/29/2007 | 8/29/2007 | A | PASS |
Troy Cobbley
|
|
|
Underground supply flush passed.
|
INSP-Sprinkler Rough-in/Hydro | 8/28/2007 | 8/29/2007 | 8/29/2007 | A | PASS |
Troy Cobbley
|
|
|
The underground hydro test passed.
|
INSP-Sprinkler Rough-in | 7/24/2007 | 7/25/2007 | 7/25/2007 | A | PART |
Forrest France
|
|
|
UG fire supply line installation is good for cover.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/18/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/18/2007 | | 7/18/2007 | | DONE |
|
|
|
|
Telephone call | | | 7/18/2007 | | DONE |
|
|
|
lft ms with lilly scales ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 7/18/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/18/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/29/2007 | | 7/17/2007 | | PASS |
|
|
|
Plans & Calculations are approved w/conditions by Bryan Johnson
|
Inspection Record Card- Fire | 6/29/2007 | | 6/29/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/6/2007 | | 6/29/2007 | | DONE |
|
|
|
Plans are approved by Bryan Johnson for UG
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/29/2007 | | DONE |
|
|
|
|
Telephone call | | | 6/29/2007 | | DONE |
|
|
|
jim came in at the time I was working on the permit and ready to be picked up
|
Permit Ready to Issue | | | 6/29/2007 | | |
|
|
|
|
Issue and Print Permit | | | 6/29/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 6/26/2007 | | |
|
|
|
|
Case Summary | | | 6/6/2007 | | DONE |
|
|
|
|
Application received | | | 6/6/2007 | | |
|
|
|
|
Pending Assignment by SAM | 6/6/2007 | | | | |
|
|
|
|