Permit Information
Permit NumberFIR07-00517
StatusFinaled
Name WESTERN STATES FIRE PROTECTION
Site Address 5761 W MARVIN LN
Project NamePARK APARTMENTS
Customer Number 
ePlanReview 
Description
Scope of Work
Install a complete overhead sprinkler system through out the existing structure in accordance with NFPA13-R and IFC 2003 . A new 6” under ground service will be run beginning from a gate vale located in the street off of S. Curtis. All fire sprinkler work and related shall be performed per NFPA 13, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to permit BLD06-03598. 06/28/07 ///09/24/07 Revised Scope of Work - This review of a previously approved plan is due to significant changes to the system which resulted in a complete resubmittal of the plans and calculations. The system type has been changed from a modified 13R type wet pipe system to a 13R Modified Anti-Freeze (Glycerine) system. The original extended coverage was calculated to 18’ x 18’; under this revision #2 & 3 dated 07/09/07 & 09-06-07 the spacing has been changed to a 16’ x 16’ maximum.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/29/200711/30/200711/30/2007APASS
DetailsTroy Cobbley
permit finaled. The light fixtures have been changed to can lights which no longer are obstructions.
INSP-Supply line flush11/21/200711/26/200711/26/2007APASS
DetailsTroy Cobbley
The hydro tests of the underground and both overhead systems passed. The underground flush passed as well.
INSP-Final Inspection11/19/200711/20/200711/20/2007PFAIL
DetailsTroy Cobbley
Sprinkler pendants are blocked by light fixtures. Both overhead and underground piping need hydro tested. The underground needs flushed. All riser details need inspected. Alarm interconnections need to be tested.
Issue and Print Permit  9/28/2007 DONE
Inspection Record Card- Fire9/25/2007 9/25/2007 DONE
Telephone call  9/25/2007 DONE
left vm for robert escue at ###-#### - permit ready and fees given
Permit Ready to Issue  9/25/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  9/25/2007 DONE
Sprinkler Plan Check9/10/2007 9/24/2007 PASS
plans are approved with conditions as submitted by bryan johnson
Plan resubmittals received  9/10/2007  
Received one copy of application and three copies of hydraulic calculations and pages FP1, FP2; taken to fire review
INSP-Sprinkler Rough-in8/27/20078/28/20078/28/2007AFAIL
DetailsTroy Cobbley
The sprinkler rough-in is ok but there have been alot of 90's added into the branchlines and the 1 1/2" main due to vaulted ceilings in each of the apartments. Also no tenting has been done. The sprinkler piping is not to be covered and resubmittals with hydraulic calculations are required prior to cover.
INSP-Sprinkler Rough-in8/20/20078/21/20078/21/2007APASS
DetailsTroy Cobbley
First floor piping is ok to cover. This is the only area inspected. There were some minor changes and per the installer as-builts are being resubmitted to the city.
INSP-Sprinkler Rough-in7/26/20077/30/20077/30/2007APART
DetailsForrest France
UG fire supply line is approved for cover, depth of bury is okay provided infill meets grade at existing landscaping on either side, also need to provide method for seismic clearance where the riser passes through the floor slab.
Inspection Record Card- Fire7/23/2007 7/23/2007 DONE
Telephone call  7/23/2007  
gave plans to wester states fire protection-7/23/07/mls
PLANS/APPL TAKEN TO FRONT DESK  7/23/2007 DONE
Telephone call  7/23/2007 DONE
tlk to robert escue ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  7/23/2007 DONE
Sprinkler Plan Check7/16/2007 7/21/2007 PASS
Plans are approved by bryan johnson
Plan resubmittals received  7/16/2007  
Received four copies of application, product info, hydraulic calcs and pages FP1 & FP2; taken to fire review
Application received  6/8/2007  
Pending Assignment by SAM6/8/2007    
Inspection Record Card- Fire7/23/2007